F403
Motor Constant 2 (secondary resistance)
Program Motor Vector Motor Model
This parameter is the measurement of the rotor resistance and is considered a
Motor Constant (unchanging). This value is used in conjunction with other
constants to tune the motor.
This setting (motor tuning) is required to use the Vector Control, Automatic
Torque Boost, or Automatic Energy-saving functions.
Motor Constant 3 (exciting inductance)
Program Motor Vector Motor Model
This parameter is used to input the excitation inductance for the motor. This
value is used in conjunction with other constants to tune the motor.
This setting (motor tuning) is required to use the Vector Control, Automatic
Torque Boost, or Automatic Energy-saving functions.
Motor Constant 4 (load inertia)
Program Motor Vector Motor Model
This parameter is used to control the load inertia during speed changes.
Acceleration and deceleration overshoot may be reduced by increasing this
value.
This setting (motor tuning) is required to use the Vector Control, Automatic
Torque Boost, or Automatic Energy-saving functions.
Motor Constant 5 (leakage inductance)
Program Motor  Vector Motor Model
This parameter provides slight increases in the output voltage of the drive at the
high speed range.
This setting (motor tuning) is required to use the Vector Control, Automatic
Torque Boost, or Automatic Energy-saving functions.
Number of Motor Poles
Program Motor Vector Motor Model
This parameter identifies the number of motor poles.
Settings:
2 — 2 Pole Motor
4 — 4 Pole Motor
6 — 6 Pole Motor
8 — 8 Pole Motor
10 — 10 Pole Motor
12 — 12 Pole Motor
14 — 14 Pole Motor
16 — 16 Pole Motor
150
Direct Access Number — F403
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — No
Minimum — 0.00
Maximum — Open
Units — m
Direct Access Number — F404
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — No
Minimum — 0.00
Maximum — 6500.0
Units — mH
Direct Access Number — F405
Parameter Type — Numerical
Factory Default — 1.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Direct Access Number — F410
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — No
Minimum — 0.00
Maximum — 650.0
Direct Access Number — F411
Parameter Type — Selection List
Factory Default — Selection 4
Changeable During Run — No
Minimum — 2
Maximum — 16
GX9 ASD Installation and Operation Manual
F411