Toshiba GX9 Installation & Operation Manual page 220

Table of Contents

Advertisement

F893
Optional Parameters 4
Program Communications Optional Parameters
Not Used.
Optional Parameters 5
Program Communications Optional Parameters
Not Used.
S20 Reset
Program Communications S20 Settings
Not Used.
Settings:
0 — Disabled
1 — Reset
Virtual Linear Pump Mode Switch
Program Virtual Linear Pump Settings
This parameter is enabled for use by completing the Virtual Linear Pump
Setup
Wizard.
During a properly configured Virtual Linear Pump operation, this parameter
establishes if feedback is used or not.
Select the command source or the feedback source for operating in the Direct
or Process modes, respectively, at F920. The default selection for each may be
used.
Note:
If
F920
is set to use VI/II as the command source DO NOT set
this parameter to Process Hold. Doing so will result in an error
message (VI cannot be used for both functions).
Note:
Once set, this parameter selection will be retained when the
Virtual Linear Pump function is turned on or off. The function is
turned on or off by activating/deactivating a discrete input
terminal that is set to Virtual Linear Pump Enable/Disable.
Settings:
0 — Disabled
1 — Direct Mode
2 — Process Hold
255 — Setup
208
Direct Access Number — F893
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 65535
Direct Access Number — F894
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 65535
Direct Access Number — F899
Parameter Type — Disabled
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F911
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
GX9 ASD Installation and Operation Manual
F911