F520
Pattern Run
Program Frequency Pattern Run
This parameter enables the configured Pattern Run selections to be run.
Groups of configured Preset Speeds may be enabled to be run from this screen.
The execution of grouped Preset Speeds in this manner is called a Pattern
Run.
One to eight user-selected Preset Speeds may be run sequentially for a user-set
number of repetitions. The group of user-selected Preset Speeds is called a
Pattern Group. The Pattern Run function executes the user-set Pattern
Group. Up to four Pattern Groups may be configured and run.
Each Pattern Group (1–4) is comprised of up to eight Selections with each
Selection being 1 of 15 possible Preset Speed settings. Skip may be selected to
ignore a Selection within a group.
This parameter enables the configured Pattern Run selections to be run. Preset
Speeds 1 – 15 are configured at
for each Preset Speed is set at
The user configures a Preset Speed that is to be used as Selection 1 (of 8) for
Pattern Group 1. See
F018
Preset Speeds 1 – 8. Preset Speeds 9 – 15 are configured at parameters
F294.
Parameters
F531
F538
are used to select the configured Preset Speeds that
are to be used to create Pattern Group 1.
Pattern Group 1 may be run and repeated up to 255 times or set to run
indefinitely by setting a repeat value at F530.
Pattern Group 1 may be programmed to repeat from the start at its conclusion
or stopped when completed (see F521).
The table to the right depicts the Preset Speed Selections and the respective
parameter number for each of the Preset Speeds that comprise
Pattern Group 1.
Using the same method as described for Pattern Group 1, setup Pattern
Groups 2 – 4 at
F540
F568
Pattern Run Setup and Execution
1.
Using parameters
F531
used for Pattern Group 1. Set any unused selections to Skip.
2.
Set the run time for each Preset Speed at
3.
Set
F520
to Enabled to enable the Pattern Run function.
4.
Set an unused discrete input terminal to Pattern Run Selection 1.
5.
Set an unused discrete input terminal to Pattern Run Trigger.
6.
Provide an F and/or R run command.
7.
Place the ASD in the Remote mode (Local/Remote LED is off).
Note:
Activation of the Pattern Run Selection 1 discrete input terminal
is required to enable Pattern Group 1 for use. Activation of the
Pattern Operation Trigger Signal discrete input terminal starts
the Pattern Group 1 pattern run.
8.
Activate the Pattern Run Selection 1 terminal.
9.
Activate the Pattern Run Trigger terminal and the Pattern Run will
engage.
GX9 ASD Installation and Operation Manual
F018
F024
and
F287
– F294. The run time
F585
– F599.
for information on configuring the individual
if more Preset Speed entries are required.
– F538, select the configured Preset Speeds to be
F585
– F599.
Direct Access Number — F520
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Units — Preset Speed Number
Pattern Group 1
Selection
F531 F532 F533 F534 F535 F536 F537 F538
1
2
3
Skip Skip Skip Skip Skip Skip Skip Skip
1
1
1
2
2
2
F287
3
3
3
4
4
4
5
5
5
6
6
6
7
7
7
8
8
8
9
9
9
10
10
10
11
11
11
12
12
12
13
13
13
14
14
14
15
15
15
Note:
Set any unused discrete input
terminal to Pattern Run
Selection 2, 3, and/or 4 as
required to increase the
number of Preset Speed cycles
required for the application.
F520
4
5
6
7
8
1
1
1
1
1
2
2
2
2
2
3
3
3
3
3
4
4
4
4
4
5
5
5
5
5
6
6
6
6
6
7
7
7
7
7
8
8
8
8
8
9
9
9
9
9
10
10
10
10
10
11
11
11
11
11
12
12
12
12
12
13
13
13
13
13
14
14
14
14
14
15
15
15
15
15
169