6.5 Printing Data in Memory
Prints out the contents of the instrument's read-write memory.
The small display indicates 01 : 01 for the OBJ : TEST number (starting address
of printing).
The main display indicates the last recording in memory (the end address of print-
ing). e.g. 12 : 06.
01 flashes opposite the OBJ position (use the and
end addresses of the printout).
•
To exit without printing, alter the position of the selector switch.
To proceed with printing, press the PRINT button once more.
•
•
To stop printing, alter the position of the selector switch.
Only the main results are printed out.
Example:
AEMC
Instruments Model 5060
®
Instrument number: 000 001
INSULATION RESISTANCE TEST
OBJECT: 01 .....................................TEST: 01
Description:.....................................................
........................................................................
Date: ............................................03.31.2001
Starting time: ......................................13h 35
Running time: .......................... 16 min 27 sec
Temperature: ................................°C .........°F
Relative humidity: ....................................... %
Test voltage: ...................................... 5000 V
Insulation resistance (IR): .................3.85 TΩ
DAR: .....................................................1.234
PI: .........................................................2.382
DD: .................................................................
Capacitance:.............................................. µF
I residual: ................................................... nA
Comments: .....................................................
........................................................................
Date of next test: ............................................
OBJECT: 01 .....................................TEST: 02
Date: ............................................03.31.2001
Starting time: ......................................15h 10
Running time: .......................... 15 min 30 sec
40