5. PARAMETERS
Class No. Symbol
14
TQC
Torque command time constant
Used to set the constant of a low-pass filter in response to the torque
command.
Torque
15
*SNO Station number setting
Used to specify the station number for serial communication.
Always set one station to one axis of servo amplifier. If one station
number is set to two or more stations, normal communication cannot
be made.
16
*BPS
Serial communication function selection, alarm history clear
Used to select the serial communication baud rate, select various
communication conditions, and clear the alarm history.
Name and function
Torque command
TQC
TQC: Torque command time constant
Serial baud rate selection
0: 9600 [bps]
1: 19200[bps]
2: 38400[bps]
3: 57600[bps]
Alarm history clear
0: Invalid
1: Valid
When alarm history clear is made valid, the alarm
history is cleared at next power-on.
After the alarm history is cleared, the setting is
automatically made invalid (reset to 0).
Serial communication standard selection
0: RS-232C used
1: RS-422 used
Serial communication response delay time
0: Invalid
1: Valid, reply sent after delay time of 800 s or more
5 - 10
WWW.NNC.IR
Initial
value
0
After
filtered
TQC
Time
0
0000
Setting
Control
Unit
range
mode
ms
0
T
to
20000
sta-
0
P S T
tion
to
31
P S T
Refer to
Name
and
function
column.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents