Frequently Used Device Commands - Lenze E84AVSC Operating Instructions Manual

Controller/inverter drive
Table of Contents

Advertisement

5.4

Frequently used device commands

The device commands available in the subcodes of C00002 serve, among other things, to
directly control the controller, to organise parameter sets, and to call diagnostic services.
Regarding the execution of the device commands, a distinction is drawn between:
 Device commands which have an immediate effect on control (e.g. "Delete logbook")
– After being called in C00002/x, these device commands provide static status
information ("On" or "Off").
 Device commands with longer execution duration (several seconds)
– After being called in C00002/x, these device commands provide dynamic status
information ("work in progress 20 %"  "work in progress 40 %", etc.).
– The execution of the device command has not finished successfully until the "Off /
ready" status information is provided in C00002/x.
– In the event of an error, the "Action cancelled" status information is provided in
C00002/x . In this case, further details can be obtained from the status of the device
command executed last which is displayed in C00003.
Parameter
C00002/1
C00002/11
C00002/19
C00002/21
C00003
C00002/1
Load Lenze setting
This device command serves to reset all parameter settings in the device to the Lenze setting in order to keep a
defined device configuration.
Note: All parameter changes which have been carried out after the last time the parameter set was saved will be
lost!
• Only possible when the controller is inhibited.
Selection list
(Lenze setting printed in bold)
C00002/11
Save all parameter sets
Note: During the storage process:
• Do not switch off the supply voltage!
• Do not remove the memory module from the device!
Selection list
(Lenze setting printed in bold)
from Firmware V06.00 - DMS 1.1 EN - 11/2011
Name
Load Lenze setting
Save all parameter sets
Reset error
Delete logbook
Status of the last device command
0 Off / ready
1 On / start
0 Off / ready
1 On / start
L
8400 StateLine C | Operating instructions
Frequently used device commands
Controller inhibit required
Info
Reset all parameters to the Lenze setting
(Restore delivery status)
Info
Save parameter settings in the memory module of the
controller safe against mains failure
Before commissioning
Status information
dynamic
dynamic
static
static
25