8400 StateLine C | Operating instructions
Before commissioning
General notes on parameters
5.2.3
Save parameter settings in the memory module safe against mains failure
Controller parameter changes via the EASY Starter /»Engineer«, the keypad, or a master
control via fieldbus communication will be lost after mains switching of the controller
unless the settings have been explicitly saved to the integrated memory module.
General information
In the delivery state, the Lenze setting of the parameters has been saved to the
integrated memory module.
When the device or the external 24 V voltage supply is switched on, all parameters are
automatically loaded from the memory module into the main memory of the
controller.
Full functionality of the memory module is even provided if the power supply has been
switched off and only the electronic components of the controller are externally
supplied by a 24 V DC voltage, e.g. via the X4/24E terminal.
Save parameters
Using the keypad, you can press function key to save the parameter settings.
The »EASY Starter«/»Engineer« serves to execute the saving via the icon
toolbar or via the device command "Save all parameter sets"
start").
– The storage process may take a couple of seconds. After the device command has
been called in C00002/11, dynamic status information ("Work in progress 20%"
"Work in progress 40%" "Work in progress 60%", etc.) is returned.
Note!
In order to prevent data inconsistencies during the saving process:
• Do not switch off the supply voltage!
• Do not remove the memory module from the device!
20
L
from Firmware V06.00 - DMS 1.1 EN - 11/2011
in the
(C00002/11
= "1: On /