Cleaning system burner

The cover of the burner must be screwed tight after service. Under no
circumstances should it be possible to lift it off by hand.
Function and service
Cut the power to the boiler before servicing. Next to the burner an air compressor is
mounted that provides pressurised air for cleaning the burner. This is done by letting high
pressure air into the burner after the burner has made a heating cycle. The compressor
builds up a pressure in the air container which is released into the burner in one blast. This
is done four times and all ash and pellet remains are blown out into the ash compartment.
The settings are made in the "Service" menu.
The compressor
The compressor creates a pressure in the
container. The compressor has a life span of at
least 2500 hours.
Air container
The air container stores the air before it is
released into the burner.
The pressure gauge
Displays the pressure in the air container.
The safety valve
Prevents the pressure exceeding 9bars by releasing
air if the pressure switch fails.
The pressure switch
Stops the compressor at a pre-set value.
Normally 7 bars. This is also adjustable.
Non return valve
Keeps the air in the container and prevents
pressure on the compressor.
1
Compressor
2
Solenoid
3
Silencer
4
Pressure Switch
5
Safety valve
6
Non return valve
7
Air container
8
Capacitor