Tuning the burner

When the auger runs, all doors must be closed and the feeding tube must be closed
also. This must be done to activate the under pressure switch
Fill feeder
Start filling the auger by setting "FILL FEEDER". The auger will run for 15 min. Put a
bucket under the outlet to prevent pellet from falling out. It is important that the auger is
filled properly, therefore it is a good idea to tap it with for example a rubber mallet during
the filling.
The fan
The rpm for the fan is set in the menu "FAN". The rpm is dependent upon the operation
dose set. For the best efficiency a flue gas analyzer should be used. You also choose if
the low power option should be activated.
Start dose
The feeding of the pellet is the most important part in the system for a good combustion
and performance. Set the start dose by activating the "RUN START DOSE". It is
important that the start dose is absolutely accurate and 40 cl. It should be checked on
startup and then verified when the boiler has been running about 60 hours. If the burner
fails to start, the feeding and start dose is the most likely cause of failure.
Boiler effect
To set the boiler effect open the "OPERATION" menu and then proceed to
"INSTALLATION" menu to set the "EFFECT HIGH SPEED". It is very important that the
boiler never is used at a higher output effect than the boiler rating allows!
Verifying effect
Open the "OPERATION menu and access the "FEEDER SETTINGS" to activate the
function "RUN OPER.DOSE". The auger will feed small doses of pellets for 6 minutes
in the same way as when it is running in operation mode. Weigh the pellets fed over this
period of time to verify the exact power output. 6 minutes is equal to 1/10 of an hour. The
equation to use is: the fed weight x 10 = Feed rate in one hour. Multiply the hourly feeding
rate with the energy containment of the pellets (normally 4,8kWh) and you have your exact
output of the boiler.
Service
In this menu the settings is deciding how and when the burner should be cleaned with the
compressed air. The less time the cleaning is set to be prevented, the better. There will be
fewer times/year the burner needs to be cleaned manually if the compressor is allowed
to do the work. Here is also the maximum time set for the burner to be running before
it cleans itself. It goes into cooling phase and cleans and then startup again. When the
settings are made, set the burner to "ON", and the first start will take place if there is a
heating need from the boiler.