Cleaning system burner

Function and service
Cut the power to the boiler before servicing. Next to the burner a air compressor is moun-
ted that provides pressurised air for cleaning the burner. This is done by letting high pres-
sure air into the burner after the burner has made a heating cycle. The compressor build up
a pressure in the air container which is released into the burner in one blast. This is made
four times and all ashes and pellet rests are blown out into the firebox. In the menu "Ser-
vice" the settings are made.
The compressor
The compressor creates a pressure in the
container. The compressor has a life span of
at least 2500 hours. It might then need to be
serviced. Effecta provides a renovating kit.
Air container
The air container stores the air before it is
released into the burner.
The pressure gauge
Displays the pressure in the air container.
The safety valve
The safety valve prevents the pressure to exceed
9bars by releasing air if the pressure switch fails.
The pressure switch
It stops the compressor at a pre-set value.
Normally 7 bars. This is also adjustable.
Non return valve
Makes the air stay in the container and not putting
pressure on the compressor.
1
Compressor
2
Solenoid
3
Silencer
4
Pressure Switch
5
Safety valve
6
Non return valve
7
Air container
8
Capacitor