Trouble shooting

There are actions that the end user can take to fix a stop. However, a professional should always be
adviced before doing any adjustments.
Fault
The burner does not ignite
The burner "puffs" at start
High temp protection on
fall shaft activated
Inner combustion tube fills up with
ashes
Ashes are totally black
Poor hot water capacity
Low/high indoor temperature
Soot in the boiler room
Alarm (flue gas)
No heat on radiators
White smoke from the chimney
The auger dont work

The sensors

The value of the resistance on the Pt1000 and NTC 22KΩ sensors is measured with ohm meter.
Disconnect the sensor from the motherboard in order to measure. Remember that the sensors
need good connection in order to get a correct result.
If the cables are lengthened, use these cables:
- For a length up to 15m 2 x 0,5m²
- For a length up to 50m 2 x 0,75m²
- Do not place these cables together with main cables(high voltage).
Temp.
0°C
10°C
20°C
30°C
40°C
50°C
Effecta AB Västra Rågdalsvägen 21 434 99 Kungsbacka Sweden +46-300 - 22320 info@effecta.se
Cause
- Incorrect start dose
- Igniter faulty
- Igniter console poorly attached
- Inner combustion tube filled with ashes
- Incorrect start dose
- Low draft
- Inner combustion tube filled with ashes
- Poor combustion
- The burner cleaning malfunctioning
- Poor combustion
- Low temperature in the boiler
- To high flow in the pipes
- Incorrect set thermostat
- Sensor untrimmed
- Placement of thermostat in a bad place
- Leaking seals
- Sooty boiler
- Poor combustion
- Broken sensor
- Shunt motor broken
- Thermostat set to low
- Low flue gas temperature
- To big chimney
- Rain water in the chimney
- Broken motor
- OH prtection fallshaft activated
- No underpressure
Pt1000
22KΩ
1000 ohm
66000 ohm
1039 ohm
41800 ohm
1077 ohm
27100 ohm
1116 ohm
18000 ohm
1155 ohm
12200 ohm
1194 ohm
8450 ohm
Action
- Adjust start dose
- Replace igniter
- Adjust the console
- Clean the burner
- Adjust start dose
- Control the draft
- Clean the burner
- Contact your installer
- Contact your installer
- Contact your installer
- Set the burners "Stop" temperature
- Adjust the flow on the mixing valve
- Changing the water tap
- Adjust thermostat
- Trim sensor (page17)
- Move the sensor to a better place
- Contact your installer
- Clean the boiler
- Contact your installer
- Contact your installer
- Contact your installer
- Adjust thermostat
- Cut turbulators/increase power
- Contact a professional
- Mount a rain hood
- Replace motor
- Check combustion
- Clean boiler
- Reset OH protection
- Check pressure switch
- Check flue
- Check chimney
- Check leakage from soot door
Temp.
Pt1000
60°C
1232 ohm
70°C
1271 ohm
80°C
1309 ohm
90°C
1347 ohm
100°C
1385 ohm
higher
22KΩ
5960 ohm
4280 ohm
3130 ohm
2320 ohm
1746 ohm