I/O Module" Tab; Figure 20: "I/O Module" Tab - WAGO SYSTEM 750 User Manual

3-phase power measurement module
Table of Contents

Advertisement

64
Commissioning
8.1.3

"I/O Module" Tab

On the "I/O Module" tab you can do two general settings for the entire I/O
module. These are "Enable watchdog" and "Enable DC measurement". The
watchdog deactivates the green status LED "A" if no process data is received
within 100 ms.
You can also specify the measuring cycle time. The minimum value is 39 ms,
default is also 39 ms. The maximum value is 24375 ms.

Figure 20: "I/O Module" Tab

WAGO-I/O-SYSTEM 750
750-493 3-Phase Power Measurement Module
Manual
Version 1.2.0

Advertisement