Control And Status Bytes; Table 17: Control Byte C0 - WAGO SYSTEM 750 User Manual

3-phase power measurement module
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-493 3-Phase Power Measurement Module
4.4

Control and Status Bytes

Table 17: Control Byte C0

Bit 7
Reg_Com
ProcDat_
ID
Channel_
ID
Reg_Com 0:
Manual
Version 1.2.0
Bit 6
Bit 5
Reserved
Channel_ID
Here, enter the process data index for the physical variable you wish to read out
using input data word 1.
0:
Current (rms)
1:
Voltage (rms)
2:
Active power
3:
Power factor
4:
Active energy
5:
Max. current
6:
Max. voltage
7:
Max. active power
8:
Frequency
9:
Min. current
10:
Min. voltage
11:
Min. active power
12 .... 15:
Reserved
Simple
Always 0
process
(With the simple process image the channel index has no significance.)
image
Flexible
Here, enter the channel index for the channel from which you wish to
process
read out a measured value using input data word 1.
image
0: Channel 1
1: Channel 2
2: Channel 3
3: Calibration mode active
Process data communication
1:
Register communication
Control Byte C0
Bit 4
Bit 3
Process Image
Bit 2
Bit 1
ProcDat_ID
29
Bit 0