Commissioning

Table 27: Register 32

Bit 0: enUserScaling
0: *
User scaling deactivated; the transformation ratio is 1:1.
1:
User scaling activated; the transformation ratio is 1: (divisor for the current
transformer ratio).
Bit 1: reserved
Bit 2: disWdTimer
0: *
Watchdog timer activated: The watchdog trips and deactivates the green status LED
"A" if no process data is received within 100 ms.
1:
Watchdog timer not activated.
Bit 3: enFlexProcImage
0: *
Simple process image (compatibility mode)
1:
Flexible process image
Bit 4: skipDCFilter
0: *
DC filter activated
1:
DC filter is bypassed
Bit 5: reserved
Bit 6: invEnergySign
0: *
Energy consumption measurement not inverted.
1:
Energy consumption measurement inverted (generating operation)
Bit 7: enClrMinMaxValues
0: *
Automatic deleting of minimum and maximum current, voltage and power values
deactivated.
1:
Automatic deleting of minimum and maximum current, voltage and power values
activated.
Bit 8 ... 15: reserved
* Factory setting

Table 28: Register 35

Scaling factor for measuring energy
750-493
0:
1 mWh
1:
0.01 Wh
2:
0.1 Wh
3:
1 Wh
4: *
0.01 kWh
5:
0.1 kWh
6:
1 kWh
≥7:
reserved
* Factory setting

Table 29: Register 36

Register 32 - Mode setting
Function
Mode setting
Register 35 - Scaling factor for measuring energy
Function
Register 36 - Undervoltage threshold
Function
Undervoltage threshold;
resolution 0.1 V
WAGO-I/O-SYSTEM 750
750-493 3-Phase Power Measurement Module
Data type
Access
Flags
R/W
Data type
Access
UINT
R/W
750-493/000-001
5 mWh
0.05 Wh
0.5 Wh
5 Wh
0.05 kWh
0.5 kWh
5 kWh
reserved
Data type
Access
UINT
R/W
Factory setting
0x0020
Factory setting
0x0004
Factory setting
0x0064 (10 V)
Manual
Version 1.2.0