WAGO SYSTEM 750 User Manual page 43

3-phase power measurement module
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-493 3-Phase Power Measurement Module
B. User Scaling ON, Measurement with Current Transformer
Current
Register 32, bit 0
Register 37 (D-CTR)
Process value
Scaling factor PI
Equation
Measured value
Active Power
Register 32, bit 0
Register 37 (D-CTR)
Process value
Scaling factor PI
Equation
Measured value
Active Energy
Register 32, bit 0
Register 37 (D-CTR)
Register 35*
Process value
Scaling factor PI
Equation
Measured value
* Register 35: Setting in the register defines the scaling factor PI for energy values
C. User Scaling OFF, Measurement with Current Transformer 500:1 A
(1A Variants) and 500:5 A (5A Variants)
D-CTR values of 500 or 100 must be taken into account externally when user
scaling is OFF, i.e. the transferred measured value must be multiplied by 500 or
100 in the high-level PLC.
Current
Register 32, bit 0
Register 37 (D-CTR)
Process value
Scaling factor PI
Equation
Measured value
Note: Resolution of the current values in 500mA steps
Manual
Version 1.2.0
750-493
1
0x002D (45)
0x96A1 (38561)
0.001 A / LSB
Measured value = Process value x Scaling factor PI
38.561 A
750-493
1
0x002D (45)
0x22A5 (8869)
0.1 W / LSB
Measured value = Process value x Scaling factor PI
886.9 W
750-493
1
0x002D (45)
2
0x0D86 (3462)
0.1 Wh / LSB
Measured value = Process value x Scaling factor PI
346.2 Wh
750-493
0
0x0001 (1)
0x01A9 (425)
0.001 A / LSB
Measured value = Process value x Scaling factor PI
x D-CTR
212.5 A
Function Description
750-493/000-001
1
0x0028 (40)
0x60FB (24827)
0.005 A / LSB
124.135 A
750-493/000-001
1
0x0028 (40)
0x1648 (5704)
0.5 W / LSB
2852.0 W
750-493/000-001
1
0x0028 (40)
4
0x2CA3 (11427)
50 Wh / LSB
571350 Wh
750-493/000-001
0
0x0001 (1)
0x033D (829)
0.005 A / LSB
414.5 A