Interpretation Of The Results - AEMC 6550 User Manual

10kv and 15kv megohmmeters
Hide thumbs Also See for 6550:
Table of Contents

Advertisement

Use the ▲▼ arrow buttons to select DAR or PI.
Total Run Time
Manual Stop
Manual Stop + DD
Timed Run (m:s)
Timed Run + DD
DAR
(s/s)
PI (m/m)
Press the CONFIG button to exit the configuration menu.
DAR or PI is displayed in the top left corner of the display unit to indicate the configuration chosen.
Press the START/STOP button to start the measurement. It stops automatically and the values of DAR and PI
are displayed.

4.6.2 Interpretation of the Results

DAR
DAR < 1.25
1 ≤ PI < 2
1.25 ≤ DAR < 1.6
2 ≤ PI < 4
1.6 ≤ DAR
4 ≤ PI
A capacitance in parallel to the insulation resistance extends the settling times of the measurements. This can
affect or even inhibit the measurement of DAR or PI (depending on the time set for recording the first resistance
value). The table below indicates the typical values of the capacitances in parallel with the insulation resistance,
making it possible to measure the DAR and the PI without changing their preset durations.
100kW
500V
10µF
1000V
5µF
2500V
2µF
5000V
1µF
10,000V
0.5µF
15,000V
0.3µF
Megohmmeter Models 6550/6555
Shop for AEMC products online at:
CONFIG
00:01:00
2:00
30/60
1.0/10
PI
Condition of insulation
PI < 1
Poor or even dangerous
Good
Excellent
1MW
10MW
10µF
10µF
5µF
5µF
2µF
2µF
1µF
1µF
0.5µF
0.5µF
0.3µF
0.3µF
ShopAEMC
www.
Total Run Time
Manual Stop
Manual Stop + DD
Timed Run (m:s)
Timed Run + DD
DAR (s/s)
PI
(m/m)
100MW
1GW
6µF
4µF
3µF
2µF
1.2µF
1µF
0.6µF
0.4µF
0.3µF
0.2µF
0.2µF
0.1µF
.ca
CONFIG
00:10:00
2:00
30/60
1.0/10
10GW
100GW
2µF
1µF
1µF
0.5µF
0.5µF
0.2µF
0.3µF
0.1µF
0.1µF
0µF
0.1µF
0µF
1.877.766.5412
39

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6555

Table of Contents