Nabco GT1175 Quick Setup Manual page 31

Hurricane slide door system
Hide thumbs Also See for GT1175:
Table of Contents

Advertisement

www.NabcoEntrances.com
Rev 8-10-16
Error
Definition
Message
ROM
Internal ROM Error: Internal
ERROR
memory error.
ERROR
Communication Error:
RESET
Communication between the
AGAIN
U30 Microprocessor Control
and the Handy Terminal is
not taking place.
EEPROM
Internal EEPROM Error:
ERROR
Internal memory error.
ERROR_4 Electric Lock Error: Activation
device was signaling the
control to open door but the
electric lock failed to unlock
or bound up ten times.
ERROR_5 Recycle Error:
was detected more than
three times at same door
position continuously.
ERROR_6 Interior Sensor Error: Sensor
connected to the Black
(61) wire is sending an
error message to the U30
Microprocessor Control.
ERROR_7 Exterior Sensor Error:
Sensor connected to the
Black/Red (62) wire is
sending an error message
to the U30 Microprocessor
Control.
Note: ERROR CODES may have been generated as the result of a hardware problem. If resetting the software as described above
does not resolve the problem, cause of the hardware malfunction must be determined and corrected. Please contact NABCO
Entrances, Inc. Toll free at 1-877-622-2694, for additional assistance.
Handy Terminal Error Messages
Problem
Door does not work.
Control does not retain
new settings from the
Handy Terminal
Door does not work.
Door does not work.
Recycle
Door does not recycle.
Door does not work but
the electric lock works by
means of a rocker switch.
Door does not work but
the electric lock works by
means of a rocker switch.
GT1175 (H105 Medium) Hurricane Quick Set-Up and Parts Guide
Resolution
Reset U30 Microprocessor Control by turning 120 VAC off
then on again OR connect the Handy Terminal and clear the
Error Message.
Reset U30 Controller by turning 120 VAC OFF then on again. If
problem persists the cables, or control and/or Handy Terminal
might be defective. Tip: Use Handy Terminal and/or Harness
on a different door.
Replace the U30 Microprocessor Control.
Reset U30 Controller by turning 120 VAC OFF then on again
OR connect Handy Terminal & clear error message OR Turning
ON/OFF switch OFF then ON again OR opening then closing
panic breakout circuit.
Reset the U30 Microprocessor Control by turning 120 VAC
OFF then on again OR connect the Handy Terminal and clear
the error message OR Turn the 'ON/OFF Switch" OFF then ON
again OR open the closing panic breakout circuit.
Replace sensor (only applies to U-30 Microprocessor Controls
with Nabco sensors).
Replace sensor (only applies to U-30 Microprocessor Controls
with Nabco sensors).
P/N C-00106
31 of 53