4.
Fasten a side-by-side mounting plate (1).
Use four of the delivered screws (2, 3).
5.
Carefully turn the two IEDs up-side down.
6.
Fasten the second side-by-side mounting plate.
Use the remaining four screws.
7.
Carefully fasten the mounting angles (4) to the sides of the IED.
Use the fixing screws available in the mounting kit.
8.
Insert the IED into the cut-out.
9.
Fasten the mounting angles with appropriate screws.

Making the electrical connection

IED connectors

Overview

The quantity and designation of connectors depend upon the type and size of the
IED. The rear cover plates are prepared with space for the maximum of HW
options for each case size and the cut-outs that are not in use are covered with a
plate from factory.
Overview
Table 1:
Basic modules
Module
Combined backplane module (CBM)
Universal backplane module (UBM)
Power supply module (PSM)
Numerical module (NUM)
Local Human machine interface (LHMI)
Transformer input module (TRM)
Analog digital conversion module (ADM)
1MRK 504 088-UEN C
Description
A backplane PCB that carries all internal signals
between modules in an IED. Only the TRM (when
included) is not connected directly to this board.
A backplane PCB that forms part of the IED
backplane with connectors for TRM (when
included), ADM etc.
Including a regulated DC/DC converter that
supplies auxiliary voltage to all static circuits.
An internal fail alarm output is available.
Module for overall application control. All
information is processed or passed through this
module, such as configuration, settings and
communication.
The module consists of LED:s, an LCD, a push
button keyboard and an ethernet connector used
to connect a PC to the IED.
Transformer module that galvanically separates
the internal circuits from the VT and CT circuits. It
has 12 analog inputs.
Slot mounted PCB with A/D conversion.
Installation and commissioning manual