ABB RET670 Installation And Commissioning Manual page 129

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK 504 088-UEN C
Installation and commissioning manual
4
X1
50% RLdFw
IEC09000735 V2 EN
Figure 55:
Operating characteristic for phase selection function, forward
direction phase-to-phase faults
Table 22:
Test points for phase-earth loop L3-E (Ohm/loop)
Test point
Value
1
X
[X1+XN]
R
0
2
X
0
R
RLdFw
3
X
0.85·[X1+XN]
R
0.85·[X1+XN]·1/tan(60°)+RFFwPE
4
X
0.85·[X1+XN]
R
-0.85·[X1+XN]·
tan (AngNegRes-90°)
5
X
RFFwPE·tan (ArgLd)
R
RFFwPE
6
X
-0.5·RLdFw·tan (ArgDir)
R
0.5·RLdFw
The table showing test points for phase-to- earth loops is used together with figure
54.
Verifying settings by secondary injection
W
(
/
phase
)
X
1
85%
5
ArgNegRes
2
7
6
ArgDir
0.5·RFFwPP
Section 13
3
ArgLd
60°
W
(
/
phase
R
IEC09000735-2-en.vsd
Comments
XN=(X
-X
)/3
0
1
R≈0.491·(X1+XN)+RFFwPE
)