1MRK 504 088-UEN C
7.4.4
Installation and commissioning manual

Self supervision HMI data

Table 10:
Signals from the General menu in the diagnostics tree.
Indicated result
Possible reason
InternFail OK
InternFail Fail
InternWarning OK
InternWarning Warning
NUM-modFail OK
NUM-modFail Fail
NUM-modWarning OK
NUM-modWarning
Warning
ADC-module OK
ADC-module Fail
CANP 9 BIM1 Fail
RealTimeClock OK
RealTimeClock Warning
TimeSync OK
TimeSync Warning
Proposed action
No problem detected.
None.
A failure has occurred.
Check the rest of the indicated results to find
the fault.
No problem detected.
None.
A warning has been
Check the rest of the indicated results to find
issued.
the fault.
No problem detected.
None.
The main processing
Contact your ABB representative for service.
module has failed.
No problem detected.
None.
There is a problem with:
Set the clock.
If the problem persists, contact your ABB
the real time clock.
representative for service.
the time
synchronization.
No problem detected.
None.
The AD conversion
Contact your ABB representative for service.
module has failed.
IO module has failed.
Check that the IO module has been
configured and connected to the IOP1- block.
If the problem persists, contact your ABB
representative for service.
No problem detected.
None.
The real time clock has
Set the clock.
been reset.
No problem detected.
None.
No time synchronization.
Check the synchronization source for
problems.
If the problem persists, contact your ABB
representative for service.
Section 7
Energizing the IED
81