Fault tracing and repair
About this chapter
This chapter describes how to carry out fault tracing and if necessary, a change of
circuit board.

Fault tracing

Information on the local HMI

If an internal fault has occurred, the local HMI displays information under Main
menu/Diagnostics/IED status/General
Under the Diagnostics menus, indications of a possible internal failure (serious
fault) or internal warning (minor problem) are listed.
Indications regarding the faulty unit are outlined in table 27.
Table 27:
Self-supervision signals on the local HMI
HMI Signal Name:
Status
INT Fail
OFF / ON
INT Warning
OFF / ON
NUM Fail
OFF / ON
NUM Warning
OFF / ON
ADMnn
READY / FAIL
BIMnn
READY / FAIL
Table continues on next page
Fault tracing and repair
Description
This signal will be active if one or more
of the following internal signals are
active; INT--NUMFAIL, INT--
LMDERROR, INT--WATCHDOG, INT--
APPERROR, INT--RTEERROR, INT--
FTFERROR, or any of the HW
dependent signals
This signal will be active if one or more
of the following internal signals are
active; INT--RTCERROR, INT--
IEC61850ERROR, INT--
TIMESYNCHERROR
This signal will be active if one or more
of the following internal signals are
active; INT--WATCHDOG, INT--
APPERROR, INT--RTEERROR, INT--
FTFERROR
This signal will be active if one or more
of the following internal signals are
active; INT--RTCERROR, INT--
IEC61850ERROR
Analog input module n failed. Signal
activation will reset the IED
BIM error. Binary input module Error
status. Signal activation will reset the IED