Releasing The Function To Be Tested; Disturbance Report; Introduction - ABB RET670 Installation And Commissioning Manual

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 13
Verifying settings by secondary injection
13.2.6
13.2.7
13.2.7.1
110

Releasing the function to be tested

Release or unblock the function to be tested. This is done to ensure that only the
function or the chain of functions to be tested are in operation and that other
functions are prevented from operating. The user can release the tested function(s)
by setting the corresponding Blocked parameter under Function test modes to No in
the local HMI.
When testing a function in this blocking feature, remember that not only the actual
function must be activated, but the whole sequence of interconnected functions
(from measuring inputs to binary output contacts), including logic and so on.
Before starting a new test mode session the user should scroll through every
function to ensure that only the function to be tested (and the interconnected ones)
have the parameters Blocked and eventually EvDisable are set to No and Yes
respectively. Remember that a function is also blocked if the BLOCK input signal
on the corresponding function block is active, which depends on the configuration.
Ensure that the logical status of the BLOCK input signal is equal to 0 for the
function to be tested. Event function blocks can also individually be blocked to
ensure that no events are reported to a remote station during the test. This is done
by setting the parameter EvDisable to Yes.
Any function is blocked if the corresponding setting in the local
HMI under Main menu/Test/Function test modes menu remains
On, that is the parameter Blocked is set to Yes and the parameter
TestMode under Main menu/Test/IED test mode remains active.
All functions that were blocked or released from a previous test
mode session, that is the parameter Test mode is set to On, are reset
when a new test mode session is started.
Procedure
1.
Browse to the Function test modes menu.
The Function test modes menu is located in the local HMI under Main menu/
Test/Function test modes.
2.
Browse to the function instance that should be released.
3.
Set parameter Blocked for the selected function to Yes.

Disturbance report

Introduction

The following sub-functions are included in the disturbance report function:
1MRK 504 088-UEN C
Installation and commissioning manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents