Parallel Voltage Regulation - ABB RET670 Installation And Commissioning Manual

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 13
Verifying settings by secondary injection
13.11.4.8
188
=
-
ul im ub im
,
,
xline il re rline il im
EQUATION2084 V1 EN
where:
ub
is the complex value of the busbar voltage
il
is the complex value of the line current (secondary side)
rline
is the value of the line resistance
xline
is the value of the line reactance
For comparison with the set-point value, the modulus of U
equation 21.
2
¦ U
¦ = (ul , re)
+ (ul , im)
L
EQUATION2086 V2 EN
4.
Inject voltage for UB equal to setting USet.
5.
Inject current equal to rated current I2Base.
6.
Confirm on the local HMI that service values for bus voltage and load current
are equal to injected quantities.
7.
Confirm that the calculated value for load voltage, displayed on the local
HMI, is equal to that derived through hand calculations.
8.
When setting OperationLDC set to On, the voltage regulation algorithm uses
the calculated value for load voltage as the regulating quantity to compare
against USet and the voltage deadband limits UDeadband and
UDeadbandInner.
9.
While injecting rated current I2Base into the IED, inject a quantity for UB
that is slightly higher then USet + |(Rline+jXLine)·I
regulating voltage U
should be issued from the IED.
10. Reduce the injected voltage for UB slightly below USet + |(Rline+jXLine)·I
and confirm that the calculated value for load voltage is below USet and a tap
change command is issued from the IED.

Parallel voltage regulation

Master follower voltage regulation
1.
For the transformers connected in the parallel group, confirm that
OperationPAR is set to MF.
2.
For parallel operation, it is also recommended to confirm for parallel group
membership, defined by setting TnRXOP in the local HMI under Main menu/
Settings/Setting group N/Control/TransformerVoltageControl(ATCC,
90)/VCPx/ParCtrl
×
-
×
,
,
2
is higher than USet, and hence no tap change command
L
1MRK 504 088-UEN C
(Equation 20)
are according to
L
(Equation 21)
|. This will ensure that the
L
Installation and commissioning manual
|
L