Disturbance Report Settings; Disturbance Recorder (Dr) - ABB RET670 Installation And Commissioning Manual

Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK 504 088-UEN C
13.2.7.2
13.2.7.3
Installation and commissioning manual
Disturbance recorder
Event list
Event recorder
Trip value recorder
Indications
If the disturbance report is set on, then its sub-functions are also set up and so it is
not possible to only switch these sub-functions off. The disturbance report function
is switched off (parameter Operation = Off) in PCM600 or the local HMI under
Main menu/Settings/General settings/Monitoring/DisturanceReport/
DisturbanceReport(RDRE).

Disturbance report settings

When the IED is in test mode, the disturbance report can be made active or
inactive. If the disturbance recorder is turned on during test mode, recordings will
be made. When test mode is switched off all recordings made during the test
session are cleared.
Setting OpModeTest for the control of the disturbance recorder during test mode
are located on the local HMI under Main menu/Settings/General settings/
Monitoring/DisturbanceReport/DisturbanceReport(RDRE).

Disturbance recorder (DR)

A Manual Trig can be started at any time. This results in a recording of the actual
values from all recorded channels.
The Manual Trig can be initiated in two ways:
1.
From the local HMI under Main menu/Disturbance records.
1.1. Enter on the row at the bottom of the HMI called Manual trig.
The newly performed manual trig will result in a new row.
1.2. Navigate to General information or to Trip values to obtain more
detailed information.
2.
Open the Disturbance handling tool for the IED in the plant structure in
PCM600.
2.1. Right-click and select Execute manual Trig in the window Available
recordings in IED.
2.2. Read the required recordings from the IED.
2.3. Refresh the window Recordings and select a recording.
2.4. Right-click and select Create Report or Open With to export the
recordings to any disturbance analyzing tool that can handle Comtrade
formatted files.
Evaluation of the results from the disturbance recording function requires access to
a PC either permanently connected to the IED or temporarily connected to the
Verifying settings by secondary injection
Section 13
111

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents