Output frequency monitor:
Output voltage (v)
= output frequency × 10 ÷ Max. output frequency (Pn-02) × (Pn-45)
Output current monitor:
Output voltage (v)
= output current × 10 ÷ Inverter rated current × (Pn-45)
Note: Since output current becomes approx. 200% maximum of the inverter rated current, output voltage
is clamped at approx. 11v when Pn-45 is used at 1.00 and the inverter rated current is exceeded. To keep
linearity, set Pn-45 to approx. 0.5 .

2.7.9 S-CURVE PATTERN SELECTION

Item Name
S-curve Pattern Selection
To prevent shock at machine starting/stopping, accel/decel S-curve pattern is enabled by the setting of
Pn-21.
Pn-21 = 0 0 X X
FREQUENCY REF.
Constant to be set
21
4th digit
3rd digit
0
0
0
1
1
0
1
1
- -
Factory Preset
0000
Contents
No S-curve characteristics.
The S-curve characteristics is 0.2 second.
The S-curve characteristics is 0.5 second.
The S-curve characteristics are 1 second.