Installation - ACP Speecon 7200M3 Manual

Table of Contents

Advertisement

1.3 INSTALLATION

CAUTION:
• Handle with care so as not to damage the inverter during transportation
• Do not hold only the faceplate (plastic section) but the die-cast section.
LOCATION
Location of the equipment is important to achieve proper performance and normal operating life.
The 7200M3 units should be installed in areas where the following conditions exist.
•Ambient temperature:
-10 to +40°C ,+14 to 104°F (For enclosed type) ,
-10 to +45ºC ,+14 to 113ºF (For open chassis type)
•Protected from rain or moisture.
•Protected from direct sunlight.
•Protected from corrosive gases or liquids.
•Free form airborne dust or metallic particles.
•Free form vibration.
•Free form magnetic noise.
MOUNTING SPACE
30mm
Unit : mm
30mm
7200M3
Fig 1.1 Mounting Space
100mm
100mm
- -
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents