Normal Starting Method; Advanced Starting Methods; Starting Several Converters Simultaneously; Jog - Parker 590 series Product Manual

Dc digital converter
Hide thumbs Also See for 590 series:
Table of Contents

Advertisement

Normal Starting Method

Note: The Converter will not start if there are alarms present, or if Terminals B8 (Program Stop)

Advanced Starting Methods

Note: The Converter will not start if there are alarms present.
Note: The Converter will not start if there are alarms present.
590 Series DC Digital Converter
To achieve a normal start of the Converter:
1. Apply 24V to Terminal C5 (Enable)
2. Apply 24V to Terminal C3 (Start)
or B9 (Coast Stop) are low, 0V.
Ensure that Program Stop and Coast Stop are valid before Start/Run is applied.

Starting Several Converters Simultaneously

1. Apply 24V to Terminal C3 (Start)
2. Use Terminal C5 (Enable) to synchronise the start-up of the Converters

Jog

1. Apply 24V to Terminal C5 (Enable)
2. Apply 24V to Terminal C4 (Jog Mode)
The Converter can be started using JOG SPEED 1, JOG SPEED 2 (allowing for two different
setpoints, or perhaps to provide an Inch Forward/Inch Reverse).
Refer to Chapter 6: "Programming Your Application" - JOG/SLACK for further information.
Also refer to the STOP RATES function block: the CONTACTOR DELAY parameter is used to
prevent multiple operations of the main contactor from rapid use of the Jog switch.

Crawl

1. Apply 24V to Terminal C3 (Start)
2. Apply 24V to Terminal C4 (Jog Mode)
Start the Converter using a crawl speed, in Forward or Reverse.
Refer to Chapter 6: "Programming Your Application" - JOG/SLACK for further information.
Operating the Converter
4-17