Terminal Information (Control Board)
Terminal
Terminal Function
Description
Digital Input 1
Current Clamp Select
This input alters the
configuration of the current
clamps. With no
connection, i.e., false,
Analog I/P 5 provides a
unipolar current limit.
When true, Analog I/P5 is
the positive current clamp,
Analog I/P 4 is the negative
current clamp
Digital Input 2
Ramp Hold
If the input is held true the
S-Ramp output is frozen at
the last value irrespective of
the Ramped Setpoint Input.
When false the S-Ramp
Output follows the Ramped
Setpoint Input with a delay
determined by the
Acceleration and
Deceleration Ramped time
parameters.
Digital Input 3
Current Demand Isolate
This input alters the drive
operation from Speed
Control to Current Control.
When digital input No. 3 is
true, analog input No. 2
provides the current
demand and the speed
loop is disconnected.
When false the speed loop
is in control and analog
input No. 2 is an auxiliary
speed setpoint.
+24V Supply
+24V
590 Series DC Digital Converter
Technical Specifications
Signal Level
+24V = True/Bipolar Clamp
0V = False/Unipolar Clamp
Threshold +16V
+24V = True/Hold
0V = False/Ramp
Threshold + 16V
+24V = True/Current
0V = False/Speed
Threshold + 16V
Maximum output current: 250mA or
750mA (power board dependent - refer
to "Auxiliary Power Supply Details").
11-13
Configurable
Terminal
Number
YES
C6
YES
C7
YES
C8
N/A
C9