Electrical Ratings - Output - Parker 590 series Product Manual

Dc digital converter
Hide thumbs Also See for 590 series:
Table of Contents

Advertisement

Electrical Ratings - Output

Model
Max Supply
Output Current
Voltage
(armature)
(V)
(A)
590/1
500
35
590/1
500
70
590/1
500
110
590/1
500
150
590/1
500
180
590/1
500
270
590/1
500
360
590/1
500
450
590/1
500
720
598/9
660
950
598/9
660
1100
598/9
660
1388
598/9
660
1600
598/9
660
1800
598/9
550
1
2300
598/9
550
1
2800
Auxiliary Power Supply Details
Control and Fan*
Supply Voltage
Reference Supplies
(for speed and current setpoints)
DC Supply:
Power Board AH385851
Power Board AH385621
Power Board AH385128
590 Series DC Digital Converter
1
Please refer to Parker SSD Drives for the selection of suitable stack assemblies.
2
The standard overload capacity available is 200% for 10 seconds, 150% for 30 seconds. The
720A chassis has no overload capacity at maximum current whereas at output currents less than
650A overload capacity is as normal.
Approximate
Power Loss
(W)
105
210
330
450
540
710
1080
1350
2160
2850
3300
4164
4800
5400
6900
8400
* AC fans are used , thus the input voltage must be suitable for the fans supplied, either 110-
120V ±10% or 220-240V ±10%.
Single phase, 50-60Hz, ±10%
110 - 120V ±10%
220 - 240V ±10%
+10V ±0.01 @ 10mA maximum
-10V ±0.01 @ 10mA maximum
+24V nominal internally regulated
Maximum output capability: 17W or 750mA
+24V nominal internally regulated
Maximum output capability: 17W or 750mA
+24V nominal internally regulated
Maximum output capability: 6W or 250mA
Technical Specifications
Overload Capacity
Field Current
Available
Rating
(armature current)
(A)
YES
10
YES
10
YES
10
YES
10
YES
10
YES
10
YES
20
YES
20
NO
2
20
YES
30
YES
30
YES
30
YES
30
YES
30
YES
30
YES
30
11-5
Max Supply Fault Rating
(A) rms Symmetrical
5000
5000
10000
10000
10000
10000
18000
18000
30000

Advertisement

Table of Contents
loading

Table of Contents