11-2
Technical Specifications

External AC Supply (RFI) Filters and Line Choke

AC supply filter and line choke part numbers for conformance with EN55011 Class A.
Armature Current Rating
(A)
35
70
110
150, 180
270
360
450
720
800
Armature Current Rating
(A)
950, 1100
1388
1600, 1800
2300
2800
Cabling Requirements for EMC Compliance
Cable Type
(for EMC Compliance)
Segregation
Length Limitations
With External Filter
Screen to Earth
Connection
Filters must only be fitted on the mains side of the contactor.
Always use the recommended external AC Line Choke.
Total Filter Watt Loss
(W)
25
75
75
158
50
50
100
100
100
AC supply filter part numbers for "non CE marked" converters.
Total Filter Watt Loss
(W)
150
200
250
350
400
Model
Power Supply
Cable
Unscreened
From all
other wiring
(clean)
Unlimited
Parker SSD Filter Part No.
1 off CO388965U035
1 off CO388965U110
1 off CO388965U110
1 off CO388965U180
1 off CO467843U340
1 off CO467843U340
2 off CO467843U340
2 off CO467843U340
3 off CO467843U340
Parker SSD Filter Part No.
3 off CO467843U340
4 off CO467843U340
5 off CO467843U340
7 off CO467843U340
8 off CO467843U340
Motor Cable
External Filter to Converter Cable
Screened/
Replace flying leads with
armoured
screened/armoured when >0.6m
From all other wiring (noisy)
50 metres
As short as possible
Both ends
Both ends
SSD EMC Line Choke
CO463036
CO463037
CO463038
CO463039
CO057960
CO057961
CO057962
CO057963
CO057963
Line Choke Requirement
2% minimum,
refer to
Parker SSD Drives
Signal/Control
Cable
Screened
From all other
wiring (sensitive)
25 metres
Converter end
only
590 Series DC Digital Converter