10.3 GOT side settings

10.3.1 Setting communication
interface (Communication
settings)
Set the channel of connecting equipment.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: Mitsubishi
• Controller Type: Set according to the Controller
Type to be connected.
• I/F: Interface to be used
• Driver: CC-Link IE Controller Network
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

10.3.2 Communication detail settings

Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
Make the settings according to the usage environment.
3.
4.
Network
Type
Network No.
Station No.
Group No.
Click!
Mode Setting
Transmission
Speed
Refresh
Interval
Retry
Timeout
Time
Delay Time
10. CC-Link IE CONTROLLER NETWORK CONNECTION
10.3.2 Communication detail settings
Item
Description
Set the network Type
*4
(Default: CC IE Control)
Set the network No.
(Default: 1)
Set the station No. of the GOT.
(Default: 1)
-
Set the operation mode of the GOT.
(Default:
Online (auto. reconnection))
-
Set the number of refreshes to
secure the send/receive data in
station units during communication.
(Default: 1ms)
Valid when [Block data assurance
per station is available.] is checked
by the control station side network
parameters of the CC-Link IE
Controller Network.
Set the number of retries to be
performed when a communication
timeout occurs.
When no response is received after
retries, a communication times out.
(Default: 3times)
Set the time period for a
communication to time out.
(Default: 3sec)
Set the delay time for reducing the
load of the network/destination PLC.
(Default: 0ms)

10.3 GOT side settings

Range
• CC IE Control
• CC IE Control
extended mode
1 to 239
1 to 120
0 (fixed)
• Online
(auto.
reconnection)
• Offline
*1
• Test station
• Self-loopback
*1
test
• Internal self-
10
*1
loopback test
*1
• Line test
*1
• H/W test
1 Gbps (fixed)
1 to 1000ms
0 to 5times
1 to 90sec
0 to 300ms
10 - 9