Advertisement

5.3 GOT Side Settings

5.3.1
Setting communication
interface (Communication
settings)
Set the channel of the connected equipment.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: Mitsubishi
• Controller Type: Set according to the Controller
Type to be connected.
• @@@
• Driver:
Ethernet(MELSEC), Q17nNC, CRnD-700, Gateway
Ethernet(FX), Gateway
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

5.3.2 Communication detail settings

Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
5 - 14
5. ETHERNET CONNECTION
5.3 GOT Side Settings
Click!
[Controller Setting] from the
5.3.2
Communication detail settings
Make the settings according to the usage environment.
Item
Description
Set the network No. of the GOT.
GOT Net No.
(Default: 1)
Set the station No. of the GOT.
GOT Station
(Default: 1)
Set the GOT IP address, subnet mask,
GOT Ethernet
default gateway, peripheral S/W
Setting
communication port No., transparent
port No.
Set the GOT port No. for the
connection with the Ethernet module.
GOT
• For Ethernet (MELSEC), Q17nNC,
Communication
and CRnD-700
Port No.
(Default: 5001)
• For Ethernet(FX), Gateway
(Default: 5019)
Set the number of retries to be
performed when a communication
timeout occurs.
Retry
When receiving no response after
retries, the communication times out.
(Default: 3times)
Specify the time period from the GOT
startup until GOT starts the
Startup Time
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a
Timeout Time
communication to time out.
*1
(Default: 3sec)
Set the delay time for reducing the
Delay Time
load of the network/destination PLC.
(Default: 0ms)
*1
To connect the GOT with the Ethernet module (Q Series) in
the one-on-one relationship using a cross cable, set
[Timeout Time] to 6sec. or longer.
Range
1 to 239
1 to 64
5.3.3GOT Ethernet
setting
1024 to 5010,
5014 to 65534
(Except for 5011 to
5013 and 49153)
0 to 5times
3 to 255sec
1 to 90sec
0 to 10000
(
10ms)