Connecting To Cc-Link Module (Qna Series) - Mitsubishi GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(2) Station information setting
*1
Item
Station type
*2
Expanded cyclic setting
*2
Exclusive station count
Remote station points
Reserve/invalid station select
Intelligent buffer select (word)
: Necessary
*1
When the [Mode] of the CC-Link module is set at [Remote
net - (Ver. 2 mode)], [Remote station points] can be set.
[Remote station points] is a setting for the remote I/O station.
The default value (32 points) must be used on the GOT.
*2
Set the same setting as that of the GOT.
POINT
POINT
POINT
When changing the network parameter
After writing the network parameter to the PLC CPU,
operate the PLC CPU either turning OFF and then ON
or resetting.
[Controller Setting] of GT Designer3
Item
Station No.
Transmission Rate
Mode
Expanded Cyclic
Number of stations occupied
Input for Error Station
Retry
Timeout Time
Delay Time
POINT
POINT
POINT
[Controller Setting] of GT Designer3
For the setting method of [Controller Setting] of GT
Designer3, refer to the following.
12.3.1 Setting communication interface
(Communication settings)
12 - 26
12. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
12.4 PLC Side Setting
Setting
necessity at
Set value
GOT
connection
Ver.2 intelligent device
station (fixed)
Single
Exclusive station 1
32 points (fixed)
No setting
(Use default value)
: As necessary
: Not necessary
Set value
1: Station No.1
0: Online 156kbps
Ver.2: Remote net (Ver.2 mode)
Single
1 Station
0: Clear
3times (Use default value)
3sec (Use default value)
0ms (Use default value)
12.4.6 Connecting to CC-Link module
(QnA Series)
This section describes the settings of the GOT and CC-
Link module (QnA Series) in the following case of system
configuration.
POINT
POINT
POINT
CC-Link module (QnA Series)
For details of the CC-Link module (QnA Series), refer
to the following manual.
Control & Communication Link System Master/
Local Module Type AJ61QBT11/A1SJ61QBT11
User's Manual
System configuration
■ [Controller Setting] of GT Designer3
<CC-Link module>
*1
(Use the default value for settings other than the following.)
Station type
: Master station
Station No.
: Station No.0
Mode setting
: Remote net mode
All connect count
: 1
Transmission speed : 156kbps
■ Switch settings of CC-Link module (QnA Series)
■ Parameter setting
*1
The CC-Link module is mounted on the base unit slot 0.
The Start I/O No. of the CC-Link module is set to "0"
<GOT> (Use the default value for settings other
than the following.)
Station type
: Intelligent device
station
Station No.
: Station No.1
Number of stations occupied : Exclusive station 1
Transmission speed
: 156kbps