Operation Via The Basic Unit (Simoreg Dc-Master Or Sinamics Dcm); Simoreg Dc-Master Parameters - Siemens SIMOREG DC-MASTER Operating Instructions Manual

Converter commutation protector
Table of Contents

Advertisement

Commissioning
7.1
Operation via the basic unit (SIMOREG DC-MASTER or SINAMICS
DCM)
The basic converter unit has setting and monitoring parameters for commissioning, operation,
monitoring and diagnostics of the SIMOREG CCP. The state of the SIMOREG CCP is signaled via
connectors and the triggering of the SIMOREG CCP or erroneous states are signaled using fault
and alarm messages.
Data is exchanged between the basic converter unit and SIMOREG CCP via the serial interface.
7.1.1

SIMOREG DC-MASTER parameters

(see below for a detailed description)
P790 *)
Protocol selection for the basic converter interface G-SST2
r799 *)
Diagnostics information for G-SST2
r812 *)
Receive data at G-SST2
n560
Software version of the SIMOREG CCP
n569
Serial number of the SIMOREG CCP
n570
MLFB (Order No.) of the SIMOREG CCP
n571
Rated supply voltage of the SIMOREG CCP
n572
Rated current of the SIMOREG CCP
n574
State of the SIMOREG CCP
n575
Display of the I2t value of the voltage limiting choppers 1 of the SIMOREG CCP
n576
Display of the I2t value of the voltage limiting choppers 2 of the SIMOREG CCP
U577
Voltage setpoint for the upper response threshold of the SIMOREG CCP chopper
U578
Voltage setpoint for the pre-charging of the SIMOREG CCP quenching capacitors
U580
Control word for commutation monitoring
U581
Diagnostics memory for the commutation monitoring
U582
Response of the commutation monitoring
U583
Test command for the SIMOREG CCP
*) For a description of these parameters, see the operating instructions SIMOREG DC-MASTER Chapter 11
Detailed description of parameters
The specified software release refers to the software release of the SIMOREG DC-MASTER
PNU
Description
n560
Software version of the SIMOREG CCP
(2560)
i001:
Version release of the SIMOREG CCP software
i002:
Version release of the SIMOREG CCP software, boot sector
n569
Serial number of the SIMOREG CCP
(2569)
i001:
1. and 2nd position of the serial number
i002:
3. and 4th position of the serial number
i003:
5. and 6th position of the serial number
i004:
7. and 8th position of the serial number
i005:
9. and 10th position of the serial number
i006:
11. and 12th position of the serial number
i007:
13. and 14th position of the serial number
i008 to i015:
i016:
Checksum of the serial number
The ASCII-Code of the serial number can be read from this parameter.
n570
MLFB (Order No.) of the SIMOREG CCP
(2570)
Here, the coding of the corresponding MLFB is displayed.
n571
Rated supply voltage of the SIMOREG CCP
(2571)
Rated supply voltage of the SIMOREG CCP stamped on the rating plate
42
ENGLISH
0
SIMOREG DC-MASTER Converter Commutation Protector
Value range
[dimension]
Graduation
0.0 to 9.9
[from SW 2.1 and higher]
0,1
[from SW 2.1 and higher]
[from SW 2.1 and higher]
250 to 254
1
[from SW 2.1 and higher]
10 to 830
[V]
1V
12.2010
No. of
See/
indices
change
Factory
(Access /
setting (FS)
state)
Type
Ind: 2
P052 = 3
Type: O2
Ind: 16
P052 = 3
Type: L2
Ind: None
P052 = 3
Type: O2
Ind: None
P052 = 3
Type: O2
Siemens AG
6RX1700-0DD74
Operating Instructions

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents