12.2010
6.4
Fuses
Fuses in the armature circuit and in the motor circuit
Recommended Siemens semiconductor fuses (depending on the SIMOREG CCP used):
Unit Order No.
(MLFB)
6RA7085-6FC00-0
6RA7091-6FC00-0
6RA7090-6KC00-0
6RA7095-6FC00-0
6RA7095-6KC00-0
Note
It is no longer recommended to use the fuse types as listed in previous editions of the SIMOREG
CCP operating instructions.
Fuses for pre-charging
10 A line protection e.g. type Diazed 5SD604
Fuses F1 and F2 in the Power Interface
Only UL-listed or UL-recognized fuses may be used in UL-listed units.
Wickmann 198 1 A / 250 V 5 x 20 mm time-lag
Wickmann 343 1 A / 250 V 6.3 x 32 mm time-lag
Schurter FSD 1 A / 250 V 5 x 20 mm time-lag order designation 0034.3987
Schurter FST 1 A / 250 V 5 x 20 mm time-lag order designation 0034.3117
6.5
Arrangement of the terminals, connectors and fuses
Module C98043-A7046 Power Interface SIMOREG CCP
C98043-A7046
S1
Siemens AG
6RX1700-0DD74
SIMOREG DC-MASTER Converter Commutation Protector
Rated
Rated
current
voltage
600 A
460 V
1200 A
460 V
1000 A
690 V
2000 A
460 V
2000 A
690 V
X165
X300
X172
56 57 58 59 60
Fuses
1U1, 1V1, 1W1
3NE3335 (560 A / 1000 V)
3NE3335 (560 A / 1000 V)
3NE3335 (560 A / 1000 V)
3NE3338-8 (800 A / 800 V)
3NE3338-8 (800 A / 800 V)
LED
H1
X29_PAR X30_PAR
Operating Instructions
Connecting
Fuses
1C1, 1D1
3NE7431-0C (350 A / 2000 V)
3NE7431-0C (350 A / 2000 V)
3NE7431-0C (350 A / 2000 V)
3NE7648-1C (525 A / 2000 V)
3NE7648-1C (525 A / 2000 V)
F1
F2
5U1 5W1 5N1
XP
ENGLISH
37