Simoreg Dc-Master Alarms; Sinamics Dcm Alarms - Siemens SIMOREG DC-MASTER Operating Instructions Manual

Converter commutation protector
Table of Contents

Advertisement

12.2010
7.1.6

SIMOREG DC-MASTER alarms

A030
Commutation fault or overcurrent condition has occurred
(active for operating states – –, I, II)
Possible causes
Line voltage dip during regenerative operation
Current control loop not optimized
A032
SIMOREG CCP not ready
(active for operating states < o4.0)
Possible causes
Voltage not available at the connections U, V, W of the SIMOREG CCP
Voltage at C-D at the SIMOREG CCP does not match the voltage C-D at the SIMOREG DC-MASTER
The quenching capacitors of the SIMOREG CCP have not reached the setpoint voltage
The parallel interface cable is not connected at the SIMOREG CCP, which is assigned the parallel switching master
No connection between the SIMOREG DC-MASTER and SIMOREG CCP via the serial interface G-SST2
No connection between parallel SIMOREG CCP units
Contents of the memory of the technical data of the SIMOREG CCP (MLFB, rated values, serial number) invalid
The I2t value of the voltage limiting chopper 1 in the SIMOREG CCP is too high (> 100 %).
The I2t value of the voltage limiting chopper 2 in the SIMOREG CCP is too high (> 50 %).
7.1.7

SINAMICS DCM alarms

A60321
SIMOREG CCP not ready
Possible causes:
1.
Voltage not available at the connections U, V, W of the SIMOREG CCP.
Trigger time: 1 s
2.
Voltage at C-D at the SIMOREG CCP does not match the voltage C-D at the SINAMICS DCM.
Trigger time: 1 s
3.
The quenching capacitors of the SIMOREG CCP have not reached the setpoint voltage.
Trigger time: 1 s
4.
The parallel interface cable is not connected at the SIMOREG CCP which is assigned to the parallel switching master .
Trigger time: 1 s
5.
No connection between the SINAMICS DCM and SIMOREG CCP via the serial interface. (The dynamic values are not
updated)
Trigger time: 1 s
6.
No connection between parallel SIMOREG CCP units.
Trigger time: 1 s
7.
Contents of the memory of the technical data of the SIMOREG CCP (MLFB, rated values, serial number) invalid.
Trigger time: immediately
11.
The I2t value (r51575) of the voltage limiting chopper 1 is too high (> 100 %).
Trigger time: immediately
12.
The I2t value (r51576) of the voltage limiting chopper 2 is too high (> 50 %).
Trigger time: immediately
20.
The pre-charging of the chopper capacitors was not able to be completed within the time set in p50089 - or the condition
according to fault value 5 is fulfilled.
Trigger time: 20 ms after fault value 5 occurs
Siemens AG
6RX1700-0DD74
SIMOREG DC-MASTER Converter Commutation Protector
Operating Instructions
Commissioning
61
ENGLISH