Manually Activating A Nac/Relay; Enabling Or Disabling Points; Control Functions - Simplex 4006-9121 Technical Manual

Fire alarm control panel
Table of Contents

Advertisement

Chapter 7. Operating
Table 7-2 Additional Point Information (Continued)
Output
a.
(LED)
System
a.
Point

Manually Activating a NAC/Relay

Follow these steps to manually turn a NAC or Relay on or
off, or set it to automatic operation.
1.
Press <MENU>.
2.
Press <NEXT> until Control/View is shown.
3.
Press <ENTER>. Use the <NEXT> or <PREV> key to
select NAC or Relay.
4.
Press <ENTER>. Use the <NEXT> or <PREV> key to
scroll through the list of points for NAC or Relay.
5.
Press <ENTER> when the point you want to turn on or
off is displayed.
6.
Press <NEXT> until a prompt similar to the following is
shown.
ENTER = Control AUX
TROUBLE
7.
Press <ENTER>. The following prompt appears.
ENTER = Accept
FN: ON
8.
Use <NEXT> to select one of the following:
ON. Use this option to turn the relay or NAC on. To
return the NAC/Relay to automatic operation, first
set it to OFF, and then reselect the point and set it to
AUTO.
OFF. Turns the relay or NAC off.
AUTO. Use this option to return the NAC or Relay
to automatic operation.

Enabling or Disabling Points

Use the following steps to enable or disable points.
1.
Press <MENU>.
2.
Press <NEXT> until Control/View is shown.
Technical Manuals Online! - http://www.tech-man.com
Press <ENTER> to view a description of
the first system point in the list. Press
NEXT to scroll through the list of points.
Press <ENTER> to view a description of
the first system point in the list. Press
NEXT to scroll through the list of points.
STEADY
3.
Press <ENTER>. Use the <NEXT> or <PREV> key to
select IDC, NAC, or Relay.
4.
Press <ENTER>. Use the <NEXT> or <PREV> key to
scroll through the list of points.
5.
Press <DISABLE/ENABLE> when the point you want
to turn enable/disable is displayed. A prompt similar to
the following appears.
IDC1
FN: [Enable]
6.
Use NEXT to toggle between Enable and Disable. Press
<ENTER>. A prompt appears asking you to confirm the
operation. Press <ENTER>. Keep the following in mind
when enabling/disabling points.
When a monitor point is disabled, any status
changes occurring on the point are ignored by the
panel. If a control point is disabled, any automatic
functions are inhibited. A disable trouble will exist
for each disabled point in the system.
When a monitor point is enabled, a 30-second
countdown will start to prevent an operator from
accidentally enabling a point that will alarm the
system. The point may be enabled immediately by
pressing <ENTER>, or the enable can be aborted
by pressing <EXIT>.

Control Functions

The panel includes the pre-programmed functions listed in
the table below. To access these functions, press the
<FUNCTION> key, and then use the <NEXT> key to scroll
through the options. Press <ENTER> to activate a function.
The table below shows the operations available in the Func-
tion menu.
Table 7-3 Control Functions
Drill
Activates the drill operation (all notifica-
tion appliances).
Manual Evacu-
Activates manual evacuation (general
ation
alarm).
City/DACT
Disconnects the city circuit or DACT
Disconnect
(causes a trouble).