Overview; Main System Board - Simplex 4006-9121 Technical Manual

Fire alarm control panel
Table of Contents

Advertisement

Chapter 1. Overview
This publication describes how to install, configure, operate, program,
and test an 4006-9101 and 4006-9121 (includes door-mounted annunci-
ator) Fire Alarm Control Panel (FACP). In cases where the installation,
wiring, or programming procedure is identical for both panels, the term
4006 is used. If the procedure applies only to a specific panel, the com-
plete product name (i.e., 4006-9121 is used).
The 4006 is a conventional fire alarm control panel. The base system
includes five Class B Initiating Device Circuits (IDCs), which may be
wired as Class A circuits with the addition of an optional Class A mod-
ule. The base system also includes two Notification Appliance Circuits
(NACs), which may be wired class A or class B. A built-in DACT pro-
vides a means for remote station or central station monitoring.
The 4006 provides audible and visible indications during alarm, super-
visory, or trouble conditions. Should any of these conditions occur, the
system activates the applicable notification appliances, LEDs, and the
panel tone-alert. The indications continue until an operator acknowl-
edges the condition.

Main System Board

The 4006 base system includes the Main System Board (MSB) mounted
in a steel enclosure with locking door.
The MSB contains everything needed for a UL-listed fire alarm system
on one board. It consists of:
System power supply (3A); 24V filtered
Five IDCs (Class B)
Two, 2A Notification Appliance Circuits (Class A or B)
DACT
Two auxiliary relay circuits
One auxiliary power tap
2x20 backlit LCD, LEDs and keypad
Service Port
Expansion power supply connection
Expansion IDC connection
Expansion port for Class A IDC adapter connection
Connection for interface to optional city card
Communication channel for remote annunciators
Battery-backed, non-volatile memory preserves logs, time/date
information, and disabled points on AC loss.
Technical Manuals Online! - http://www.tech-man.com
In This Chapter
Environmental Specifications . . . . . . . . . . . . . .1-2
Option Modules . . . . . . . . . . . . . . . . . . . . . . . .1-2
4009-9201/4009-9202CA NAC Extender. . . . .1-2
Initiating Devices . . . . . . . . . . . . . . . . . . . . . . .1-3
User Interface. . . . . . . . . . . . . . . . . . . . . . . . . .1-3
Logging In and Out. . . . . . . . . . . . . . . . . . . . . .1-5
Overview - Programming a Job . . . . . . . . . . . .1-5
1-1