4010 System Reference with 4009 IDNet NAC Extenders

IDNet communications
to up to 5 total 4009
IDNet NAC Extenders
4009 IDNet
NAC Extender
(if required)
IDNet communications
MANUAL
RELEASE
Supervised IAM with
optional Abort Switch
IDNet Addressable devices
4090-9005/-9006 Suppression
Release Peripheral (SRP)
Horn and strobe NACs;
4 NACs standard, up to
RELEASING
8 NACs available
CAUTION
D ISC ONN ECT
POW ER
BEF ORE
SERVICING
4009 IDNet NAC EXTENDER
TM
FIRE SUPPRESSION
SYSTEM ABORT
PUSH AND HOLD
** SYSTEM I S NORMAL **
12:02:15pm
Mon 8-Mar-99
FIRE
SYSTEM
S YSTEM
ALARM
AC
ALARM
SUPERVISORY
T ROUBLE
S ILENCED
POWER
ALARM
S UPV
TROUBLE
ALARM
SYSTEM
ACK
ACK
ACK
SILENCE
RESET
SUPPRESSION RELEASE PANEL
CAUTION: This Control Unit has been arranged for releasing
service. Disable all releasing device circuits prior to servicing.
4010 Control Panel with
Suppression Release Appliqué
FIRE
NORMAL
0
DISC./
DEVICE
1
DISABLE
FIRE SUPPRESSION
DISCONNECT / DISABLE
Dedicated
NAC
MANUAL
RELEASE
24 VDC for Maintenance Disconnect
status indicator (if required)
IDNet communications
Dedicated NAC wiring To SRP, either from 4010
(dashed line) or from 4009 IDNet NAC Extender
Suppression Release Appliqué wording:
SUPPRESSION RELEASE PANEL
CAUTION: This Control Unit has been arranged for releasing
service. Disable all releasing device circuits prior to servicing.
FIRE ALARM
CONTROL
NAC for horn control
CAUTION
D ISC ON NEC T
POWER BEFOR E
SER VIC IN G
NAC for strobe control
4
Actuator Control Circuit
Agent source
Coil supervisory
module
Actuator
COIL SUPERVISION MODULE (2 AMP) 2081-904 6
RED
INSTALLATION INSTRUCTIONS 574-437 REV
YEL
NAC+
MAINTAIN 1/4" SEPARATION
BETWEEN POWER LIMITED
(RED/BLK) AND NONPOWER
S
LIMITED (YEL/BLK) WIRING
DATE CODE:
519-958
BLK
NAC-
BLK
SIMPLEX T IME RECORDER CO. GARDNER MA. USA
Agent discharge path
FIRE SUPPRESSION
SYSTEM ABORT
PUSH AND HOLD
Use separate NACs
for horn and strobe
control to implement
audible escalation of
events