Simplex 4006 Series User Manual

Simplex 4006 Series User Manual

Fire alarm control panels

Advertisement

UL, ULC, CSFM Listed; FM Approved;
MEA (NYC) Acceptance*

Features

Control panel operator convenience features:
 Wide viewing angle 2 x 20 (40 character) alphanumeric
LCD and dedicated LEDs provide convenient panel
status information
 Operation is programmable using a multi-function
keypad and the panel LCD or via service computer (PC)
 RS-232 service port provides upload/download PC
access for panel configuration and event history logs
 Software updates are via PC download
 Convenient library of standard custom label terms
 Standard on-board DACT provides: Contact ID, 3/1, 4/2,
BFSK, and SIA formats
 WALKTEST silent or audible system test
 Voltage and current for both the battery charger and the
battery can be displayed at the front panel LCD
Five Standard Initiating Device Circuits (IDCs):
 Five Class B IDCs with optional expansion to ten, all
with individual zone disable
 Monitor 2-wire or 4-wire initiating devices including
TrueAlarm smoke detectors
 Optional Class A Adapter Module
Two Standard Notification Appliance Circuits (NACs):
 Class A or Class B outputs with solid state overcurrent
protection per NAC, each rated for 2 A
 Selectable for Simplex
®
horn/strobe control or synchronized strobe control
Standard Power Supply:
 Provides 3 A maximum @ nominal 24 DC
 Automatic input power selection operates with 120 VAC
or 240 VAC, 50 or 60 Hz
 On-board temperature compensated battery charger for
up to 12.7 Ah batteries in cabinet (UL and ULC) and up
to 25 Ah batteries in separate cabinet (UL only)
Additional standard features:
 Programmable Active Status Reminder
 Two auxiliary relays
 IDCs, NACs, and Relay outputs are power limited (AC
input, battery circuits, and City Circuit Module outputs
are non-power limited)
 Available with beige or red cabinet
 UL listed to Standard 864
Available option modules:
 Door mounted 24 LED annunciator (standard on ULC
models)
 3 A Expansion Power Supply with two on-board 2 A
NACs that operate the same as standard NACs
SmartSync two-wire
LifeAlarm Fire Alarm Control Panels
4006 Series Fire Alarm Control Panels
Providing up to Ten IDCs and Four NACs
FIRE
SYSTEM
ALARM
SUPERVISORY
ALARM
SUPV
ACK

4006-9102 (Beige) Standard Control Panel

F i r e
A l a r m
A n n u n c i a t o r
FIRE
SYSTEM
ALARM
SUPERVISORY
ALARM
SUPV
ACK

4006-9122 (Beige) Control Panel with 24 LED Annunciator

Available option modules (Continued):
 Expansion IDC module with five Class B IDCs
 Class A IDC Adapter Module, City Interface Module,
and Auxiliary Relay Module
 Remote LCD and LED/Switch Annunciators

Description

For areas requiring from five to ten initiating zones, the
Simplex 4006 Series fire alarm control panels provide
flexible initiating circuit monitoring, extensive
programmable control capability, and LCD annunciated
circuit-specific 20 character custom labels.
*
See page 2 for additional ULC and MEA information. This product has been approved by
the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California
Health and Safety Code. See CSFM Listing 7165-0026:318 for allowable values and/or
conditions concerning material presented in this document. It is subject to re-examination,
revision, and possible cancellation. Additional listings may be applicable, contact your local
Simplex product supplier for the latest status. Listings and approvals under Simplex Time
Recorder Co. are the property of Tyco Fire Protection Products.
SYSTEM
ALARM
AC
TROUBLE
SILENCED
POWER
TROUBLE
ALARM
SYSTEM
ACK
ACK
SILENCE
RESET
SYSTEM
ALARM
AC
TROUBLE
SILENCED
POWER
TROUBLE
ALARM
SYSTEM
ACK
ACK
SILENCE
RESET
CAUTION
DISCONNECT
BATTERY AND
A. C. POWER
BEFORE
SERVICING
S4006-0001-8 8/2012

Advertisement

Table of Contents
loading

Summary of Contents for Simplex 4006 Series

  • Page 1  Door mounted 24 LED annunciator (standard on ULC revision, and possible cancellation. Additional listings may be applicable, contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time models) Recorder Co. are the property of Tyco Fire Protection Products.
  • Page 2 30 Power Supply and Battery Charger Simplex current-limited smoke detectors or electronic heat is 3 A @ 24 VDC for panel use. The temperature detectors (see list on page 4) as well as manual stations and compensated battery charger (sealed lead-acid batteries other compatible contact closure initiating devices.
  • Page 3 Keyboard Reference FIVE STATUS INDICATOR LEDs provide system status indications in addition to LCD information, LEDs flash to indicate the condition and then when acknowledged, remain on until reset THREE PROGRAMMABLE LEDs 2 X 20 LCD READOUT, LED backlighted during normal conditions and abnormal provide custom labeling (labels insert into a pocket), the top two LEDs are operating conditions, provides up to 20 characters for custom label information...
  • Page 4 Provides remote NACs; includes power supply and battery charger; 4009 Series Remote NAC Extender S4009-0002 4 extenders max/NAC; 4006 uses NAC output to provide control Note: Contact your local Simplex Product Supplier for additional compatible peripherals. S4006-0001-8 8/2012...
  • Page 5 Supervisory and Alarm Currents Model Module Supervisory Alarm 4006-9101 160 mA Standard fire alarm control panel 130 mA 4006-9102 + 60 mA per IDC in Alarm 4006-9121 210 mA Control panel with 24 LED Annunciator 148 mA 4006-9122 + 60 mA per IDC in Alarm 4006-9801 Expansion Power Supply 50 mA...
  • Page 6 TROUBLE Detailed NAC Ratings NAC Ratings, Maximum per NAC Appliances Simplex 4901 Series (horns) and 4906 Series Multi-Candela non-addressable Special Application: 2 A; strobe synchronization is UL listed across all 4 strobes, horn/strobes, and speaker/strobes (contact your Simplex product system NACs for these 4906 Series appliances representative for compatible appliances) Regulated 24 VDC: 1.5 A...
  • Page 7 SmartSync 2-wire horn/strobe control; horn on until silenced, strobe on until reset Provides Wheelock strobe synch protocol when using only Wheelock strobes on panel, not to be mixed with WHEELOCK Simplex strobes UTILITY Utility signal, generic non-alarm Relay Operation Modes The following relay operations are selectable from either the front panel or the PC programmer.
  • Page 8 1-1/2" (38 mm) minimum from wall surface TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. S4006-0001-8 8/2012 Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA www.simplexgrinnell.com...