Power Supply Output and Zone/Relay Module Details

Power Supply Output Details:
RUI Communications
at up to 2500 ft (762 m) for single run, or 10,000 ft
(3048 m) total if wiring is Class B and T-tapped;
selectable as Class B or Class A
Compatible RUI remote equipment
4606-9202 and 4606-9205 Color Touchscreen
Annunciators (up to 6 total), 4100 Series 24 I/O and
LED/Switch modules, 4602 Series LED/Switch and I/O
Annunciator modules, including 4602-9101 Status
Command Units (SCU), and 4602-9102 Remote
Command Units (RCU)
provides electrically isolated
IDNet+ SLC Output
Class B or Class A communication; standard capacity is
up to 100 addressable points with expansion for up to
250 points using up to two 4007-9803 IDNet+ Loop
Expansion Modules (as described on page 4)
This includes current for: special
6 A Output Rating.
application notification appliances; IDNet devices;
module currents; and auxiliary output current (battery
charging, CPU, and power supply current does not
subtract from the 6 A); when NACs are controlling
Regulated 24 DC Appliances, total NAC current
available is 3 A
Four on-board Class B/Class A NACs,
for Special Application appliances; selectable for
SmartSync horn and strobe control, or strobe
synchronization; rated 2 A each for Regulated 24 DC
appliances

Product Selection

Model*
Color
4007-9101(BA)
Red
4007-9102(BA)
Platinum
* Models with (BA) are available assembled in the USA by adding the suffix "BA".

Module and Accessories Selection Information

Factory
Model
Programming
4007-8810
Options
4007-0831
Field Installed Optional Modules (refer to diagram on page 7 for module locations)
Model
Description
Eight Point Zone/Relay Module, each point is selectable as an IDC input or Relay output, Class A IDCs
4007-9801
require 2 points (one out and one return); one module is included as standard, select up to 3 additional;
current shown is for 8 Class B IDCs with 4 in alarm, detector current is added separately
25 VDC Regulator Module; 2 A maximum output; use to power Zone/Relay modules
4007-9802
connected to initiating devices requiring nominal 25 VDC voltage; refer to technical
publication 579-832, 2-Wire Detector Compatibility Chart for application details
IDNet+ Loop Expansion Module; provides an additional isolated loop with short circuit isolation to the
4007-9803
existing IDNet+ channel, also provides an additional 75 addressable points to the IDNet+ channel
capacity, maximum of two
Panel Mounted 48 LED Status Annunciator Module; provides 24 Yellow LEDs, 20 Red
4007-9805
LEDs, and 4 Red/Green LEDs that are programmable for up to 24 IDC zones of alarm
and trouble annunciation, or as required for custom annunciation requirements
SDACT Module for Point or Event Reporting; order 2080-9047 connection cables as required (see cable
4007-9806
details under accessories)
4007-9807
City Circuit Module with Disconnect Switch
4007-9808
City Circuit Module without Disconnect Switch
4007-9809
Relay Module; relays for Alarm, Supervisory, and Trouble; rated 2 A resistive @ 32 VDC
Dual RS-232 Interface Module; Compatible with Simplex remote printer, PC annunciator or third party
4007-9812
interface (two ports/connections maximum)
controls up to 10 remote devices
includes:
rated 3 A each
Description
4007ES Hybrid with 4 conventional 3 A NACs and a 6 A output power supply/battery
charger; includes IDNet+ communications for 100 addressable points and 1, 4007-9801
Zone/Relay module; Note: Add optional module and other currents separately for battery
calculations; base panel current does not subtract from the 6 A power available for
optional modules and external loads
Description
Factory Programming (select)
Custom Labels and Programming (requires 4007-8810)
Power Supply Output Details (Continued):
 NAC end-of-line (EOL) resistor values are selectable as:
10 kΩ, 3.9 kΩ, 4.7 kΩ, 5.1 kΩ, 5.6 kΩ, or 15 kΩ
is dual rate, temperature compensated,
Battery Charger
and charges up to 18 Ah sealed lead-acid batteries
mounted in the battery compartment, and charges up to
33 Ah batteries mounted in an external cabinet
Battery and Charger Monitoring
charger status and low or depleted battery conditions;
status information provided to the master controller
includes analog values for: battery voltage, charger
voltage and current, actual system voltage and current,
and NAC current
Low Battery Voltage Cutout
required (required for ULC listing applications)
2 A Auxiliary Output (AUX/SNAC)
as resettable auxiliary power of 2 A @ 24 VDC, or
selected to be a simple NAC (SNAC) for sounder base
power, 4-wire detector power, or door holder power
Zone/Relay Module Details:
Select as IDC or Relay
IDCs, or up to 4, Class A IDCs; or up to 8, Relay outputs
rated 2 A resistive @ 30 VDC (N.O. or N.C.); or
combinations of IDCs and Relays; each zone is
separately configurable as an IDC or Relay output
Each IDC supports up to 30, two-wire
IDC Support.
devices
IDC EOL resistor values are selectable as:
2 kΩ, 2.2 kΩ, 3.4 kΩ, 3.9 kΩ, 4.7 kΩ, 5.1 kΩ, 5.6 kΩ,
6.34/6.8 kΩ, and 3.6 kΩ + 1.1 kΩ; see instructions for
more details
5
includes battery
is selectable when
can be selected either
; configure up to 8, Class B
3.3 kΩ,
Supv.
Alarm
145 mA
190 mA
Supv.
Alarm
83 mA
351 mA
max
with 1 module
190 mA
445 mA
with 2 modules
290 mA
801 mA
with 3 modules
390 mA
1156 mA
NA
no LEDs on
10 mA
10 mA
with
1.75 mA per LED,
LEDs on
105 mA max
30 mA
40 mA
20 mA
36 mA
20 mA
36 mA
15 mA
37 mA
60 mA
60 mA
S4007-0001-10 1/2017
max