Simplex 4006-9121 Technical Manual page 39

Fire alarm control panel
Table of Contents

Advertisement

3.
Use the <NEXT> and <PREV> keys to scroll through
the choices until [Edit] is displayed.
<ENTER>=Accept
IDC: [Edit]
4.
Press Enter. Information on the first IDC in the list
appears.
IDC1
Fire
The top line shows the custom label assigned to the first
IDC point (IDC1 in the example). Use the <NEXT> and
<PREV> keys to scroll through the list of IDC circuits.
5.
Press <ENTER> when the appropriate IDC is dis-
played. A prompt appears, asking you to specify the
function type.
IDC1
Fn: [Function]
6.
Press <ENTER> and use the <NEXT> and <PREV>
keys to scroll through the choices shown in Table 3-1.
The default function type assigned to all IDCs is FIRE.
7.
Pressing <ENTER> will accept any changes made and
exit, and the <EXIT/CLEAR> key quits editing without
saving.
Note: Refer to table located at top of Page 3-1 for
UL 864 compliant options.
Table 3-1 IDC Function Types
Function
Type
FIRE
WATER
HEAT
DUCT
Technical Manuals Online! - http://www.tech-man.com
M1
Device State = Status
Normal = NORMAL
Abnormal = FIRE
Short = FIRE
Open = TROUBLE
Normal = NORMAL
Current Limited = FIRE
Short = FIRE
Open = TROUBLE
Normal = NORMAL
Current Limited = FIRE
Short = FIRE
Open = TROUBLE
Normal = NORMAL
Current Limited = FIRE
DUCT Detector
Short = FIRE
Open = TROUBLE
Chapter 3. Programming IDCs, NACs, and AUX Relays
Function
Type
PULL
SMOKE
SO
WSO
SUPV
UTIL
TROUBLE
VSMOKE
Description
See note
below.
Fire Monitor
Zone
Waterflow
Monitor
STYLEC
Zone
Heat Detector
Zone
LATSUPV
Zone
3-3
Table 3-1 IDC Function Types
Device State = Status
Normal = NORMAL
Current Limited = FIRE
Short = FIRE
Open = TROUBLE
Normal = NORMAL
Current Limited = FIRE
Short = FIRE
Open = TROUBLE
Normal = NORMAL
Current Limited = Supervisory
Short = Supervisory
Open = TROUBLE
Normal = NORMAL
Current Limited = Supervisory
Short = Alarm
Open = TROUBLE
Normal = NORMAL
Abnormal = SUPERVISORY
Short = SUPERVISORY
Open = TROUBLE
Normal = OFF
Abnormal = ON
Short = ON
Open = TROUBLE
Normal = NORMAL
Abnormal = TROUBLE
Short = TROUBLE
Open = TROUBLE
Normal = NORMAL
Abnormal = VERIFY
Short = FIRE
Open = TROUBLE
Normal = NORMAL
Abnormal = FIRE
Short = TROUBLE
Open = TROUBLE
Normal = NORMAL
Abnormal = SUPERVISORY
Short = SUPERVISORY
Open = TROUBLE
Description
Pull Station Zone
Smoke Detector
Zone
Sprinkler
Supervisory
Zone
Combination
Waterflow &
Water Supervi-
sory Zone
Supervisory
Monitor
Supervised
Utility Monitor
Trouble Monitor
Verified fire
alarm - the
abnormal (cur-
rent-limited)
state causes the
alarm verifica-
tion cycle to
start. A short is
an immediate
alarm.
Style C Fire
Monitor
Latching Super-
visory Monitor
(supervisory
latches until
System Reset).