Chapter 2. Installation and System Checkout
City Connect Module Wiring
•
City connect module mounts to the main system as
shown. Refer to City Module Installation Instructions
for details.
•
City module consists of two circuits that are jumper-
configured. Circuits may be configured for reverse-
polarity or local energy operation. See jumper setting
table for details. Modules must also be added to the sys-
tem configuration. See "System Options" later in this
manual.
•
All wiring to be per NPFP-72, NEC, and local codes.
Minimum 20 AWG for reverse polarity; minimum 18
AWG for local energy circuits.
Technical Manuals Online! - http://www.tech-man.com
EMPLOY A 14.5 OHM TRIP COIL.
P3
P5
10
9
10
9
8
7
8
7
LE
LE
6
5
6
5
P2
P4
RP
RP
4
3
4
3
LE
LE
2
1
2
1
RP
RP
Figure 2-13
•
Conductors must test free of all grounds.
•
Wiring is supervised for opens and grounds, but not
power-limited.
•
For specific information about reverse polarity and local
energy circuits, see Figure 2-13.
•
If wiring is routed outside the building, use of a listed
secondary protector is required. Use Simplex 2081-
9028 or 2081-9044. A protector must be installed at
each building exit/entrance. Each 2081-9028 adds .2
ohms wiring resistance. 2081-9044 adds 6 ohms wiring
resistance. Use of 2081-9044 will greatly reduce wiring
distance.
•
Circuits are shipped with 3.3K, 1/2W resistor installed.
Remove resistor before wiring circuit. Leave installed
on unused circuits.
City Connect Module Wiring
2-12