Chapter 2. Installation and System Checkout

City Connect Module Wiring

City connect module mounts to the main system as
shown. Refer to City Module Installation Instructions
for details.
City module consists of two circuits that are jumper-
configured. Circuits may be configured for reverse-
polarity or local energy operation. See jumper setting
table for details. Modules must also be added to the sys-
tem configuration. See "System Options" later in this
manual.
All wiring to be per NPFP-72, NEC, and local codes.
Minimum 20 AWG for reverse polarity; minimum 18
AWG for local energy circuits.
Technical Manuals Online! - http://www.tech-man.com
EMPLOY A 14.5 OHM TRIP COIL.
P3
P5
10
9
10
9
8
7
8
7
LE
LE
6
5
6
5
P2
P4
RP
RP
4
3
4
3
LE
LE
2
1
2
1
RP
RP
Figure 2-13
Conductors must test free of all grounds.
Wiring is supervised for opens and grounds, but not
power-limited.
For specific information about reverse polarity and local
energy circuits, see Figure 2-13.
If wiring is routed outside the building, use of a listed
secondary protector is required. Use Simplex 2081-
9028 or 2081-9044. A protector must be installed at
each building exit/entrance. Each 2081-9028 adds .2
ohms wiring resistance. 2081-9044 adds 6 ohms wiring
resistance. Use of 2081-9044 will greatly reduce wiring
distance.
Circuits are shipped with 3.3K, 1/2W resistor installed.
Remove resistor before wiring circuit. Leave installed
on unused circuits.
City Connect Module Wiring
2-12
1
2
P6
3
4