Wiring Battery Power - Simplex 4006-9121 Technical Manual

Fire alarm control panel
Table of Contents

Advertisement

Wiring Battery Power

The main battery harness connects the main system
board to the battery set in the same cabinet.
The system requires 24V battery backup. Use two 12V
batteries, connected in series. The main battery harness
connects to the .250" fast-on battery terminals, as fol-
lows:
1.
Connect black wire to the negative battery terminal
of Battery 1
2.
Connect white wire from the positive battery termi-
nal of Battery 1 to the negative battery terminal of
Battery 2.
3.
Connect the red wire to the positive battery termi-
nal of Battery 2.
Connect the main battery harness to the four-position
header, located approximately in the center of the bot-
Technical Manuals Online! - http://www.tech-man.com
TB1
TB2
1
2
3
4
5
6
7
8
1
2
3
4
5
MAIN SYSTEM BOARD - CONVENTIONAL (MSB - C)
DANGER
HIGH VOLTAGE
IN THIS AREA
R
B
E
L
D
K
R
B
E
L
D
K
CONNECT TO
BATTERY TERMINALS
(FUSED ON PCB)
Figure 2-16
Chapter 2. Installation and System Checkout
tom edge on the main system board. Insert the connec-
tor left-justified, with the red wire to the left.
The EPS connects to the battery header next to the bat-
tery harness described in the previous bullet. Install the
EPS red/black harness right-justified to the battery
header, with the black wire to the right.
Battery circuit is supervised, but not power-limited.
For depleted battery cutout operation, remove jumper
per installation instructions. Separate jumper removal
required for main system board and EPS. System pro-
gramming option "Depleted Battery Cutout" must also
be selected. ULC-S527 depleted battery operation
requires jumper removal.
For 18 Ah or larger batteries, the 4009-9801 external
battery cabinet must be used. Mount the battery box
within 20 feet of the control panel, in accordance with
the mounting instruction label in the box. All intercon-
necting wiring must be enclosed in conduit.
TB2
6
7
8
1
2
3
4
5
6
7
8
9
10
DACT TELEPHONE
CONNECTIONS
1
2
3
4
5
6
7
8
TB5
734 - 180
ATTACH TO BATTERY CONNECTOR
RIGHT - JUSTIFIED, BLACK WIRE TO THE RIGHT
BLACK
RED
Battery Connections
2-15
THE POWER SUPPLY MODULE, PART OF THE EPS
ASSEMBLY , IS MOUNTED BENEATH THE NAC MODULE
PORTION OF THE EPS ASSEMBLY .
EPS
POWER SUPPLY MODULE
3B+
3B-
3A+
3A-
4B+
4B-
4A-
4A-
24V
0V
HARNESS 734 - 180
FROM EPS (LOWER MODULES)
TO MAIN SYSTEM BOARD
BATTERY CONNECTOR