Power Supply Output And Zone/Relay Module Details; Product Selection; Module And Accessories Selection Information - Simplex 4007-9201BA Manual

Fire control panels.fire detection and control with addressable initiation and addressable notification.
Table of Contents

Advertisement

Power Supply Output and Zone/Relay Module Details

Power Supply Output Details:
RUI Communications
at up to 2500 ft (762 m) for single run, or 10,000 ft
(3048 m) total if wiring is Class B and T-tapped; output
is selectable as Class B or Class A
Compatible RUI remote equipment
4606-9202 and 4606-9205 Color Touchscreen
Annunciators (up to 6 total), 4100 Series 24 I/O and
LED/Switch modules, 4602 Series LED/Switch and I/O
Annunciator modules, including 4602-9101 Status
Command Units (SCU), and 4602-9102 Remote
Command Units (RCU)
provides electrically isolated
IDNet+ SLC Output
Class B or Class A communication; standard capacity is
up to 100 addressable points with expansion for up to
250 points using up to two 4007-9803 IDNet+ Loop
Expansion Modules (as described on page 4)
is dual rate, temperature
Battery Charger
compensated, and charges up to 18 Ah sealed lead-
acid batteries in the battery compartment, and charges
up to 33 Ah batteries in an external cabinet

Product Selection

Model*
Color
4007-9201(BA)
Red
4007-9202(BA)
Platinum
* Models with (BA) are available assembled in the USA by adding the suffix "BA".

Module and Accessories Selection Information

Model
Factory
Programming
4007-8810
Options
4007-0831
Field Installed Optional Modules
Model
Description
Eight Point Zone/Relay Module; each point is selectable as an IDC input or Relay output, Class A
IDCs require 2 points (one out and one return); select up to 4 maximum; current shown is for 8 Class
4007-9801
B IDCs with 4 in alarm, detector current is added separately (refer to 4007ES Hybrid data sheet
S4007-0001 for additional information)
25 VDC Regulator Module; 2 A maximum output; use to power Zone/Relay
modules connected to initiating devices requiring nominal 25 VDC voltage; refer to
4007-9802
technical publication 579-832, 2-Wire Detector Compatibility Chart for application
details
IDNet+ Loop Expansion Module; provides an additional isolated loop with short circuit isolation to
4007-9803
the existing IDNet+ channel, also provides an additional 75 addressable points to the IDNet+ channel
capacity, maximum of two
Dual Class A IDNAC Isolator (DCAI); converts a single Class B IDNAC SLC input to two Class A or
two Class B SLC outputs; provides short circuit isolation between each Class A or B output circuit;
4007-9804
requires one IDNAC address; the total current remains controlled by the Class B input source SLC at
3 A maximum
Panel Mounted 48 LED Status Annunciator Module; provides 24 Yellow LEDs,
4007-9805
20 Red LEDs, and 4 Red/Green LEDs that are programmable for up to 24 IDC zones of
alarm and trouble annunciation, or as required for custom annunciation requirements
SDACT Module for Point or Event Reporting; order 2080-9047 connection cables as required (see
4007-9806
cable details under accessories)
4007-9807
City Circuit Module with Disconnect Switch
4007-9808
City Circuit Module without Disconnect Switch
4007-9809
Relay Module; relays for Alarm, Supervisory, and Trouble; rated 2 A resistive @ 32 VDC
controls up to 10 remote devices
includes:
Description
4007ES with a 3 A, Class B, IDNAC SLC for up to 127 addressable notification
appliances, and 4 A output power supply/battery charger; includes IDNet+
communications for 100 addressable points
Note: Add optional module and other currents separately for battery calculations; base
panel current does not subtract from the 4 A power available for optional modules and
external loads
Description
Factory Programming (select)
Custom Labels and Programming (requires 4007-8810)
(refer to diagram on page 8 for module locations)
Power Supply Output Details (Continued):
Battery and Charger Monitoring
charger status and low or depleted battery conditions;
status information provided to the master controller
includes analog values for: battery voltage, charger
voltage and current, actual system voltage and current,
and IDNAC SLC current
Low Battery Voltage Cutout
required (required for ULC listing applications)
4 A Output Rating.
controlled notification appliances; IDNet devices;
module currents; and auxiliary output current (battery
charging, CPU, and power supply current are not
subtracted from the 4 A)
2 A Auxiliary Output (AUX/SNAC)
either as resettable auxiliary power of 2 A @ 24 VDC,
or selected to be a simple NAC (SNAC) for sounder
base power, 4-wire detector power, or door holder
power
6
includes battery
is selectable when
This includes current for: IDNAC
can be selected
Supv.
180 mA
Supv.
83 mA
350 mA
max
with 1 module
190 mA
445 mA
with 2 modules
290 mA
801 mA
with 3 modules
390 mA
1156 mA
NA
8.3 mA
18.5 mA
no LEDs on
10 mA
10 mA
with
1.75 mA per LED,
LEDs on
105 mA max
30 mA
40 mA
20 mA
36 mA
20 mA
36 mA
15 mA
37 mA
continued on next page
S4007-0002-6 11/2015
Alarm
185 mA
Alarm
max
NA