Suppression Release Peripheral Wiring Reference

Maximum Release Appliance Circuit (RAC) Wiring Distances from Suppression Release Peripheral to
the Valve Solenoid (based on a total drop of 0.6 V)
RAC Output Current
(refer to solenoid
rating)
0.50 A
0.75 A
1.00 A
Metric wire equivalents: 18 AWG = 0.82 mm
NORMAL
0
DISC./
1
DISABLE
FIRE SUPPRESSION
DISCONNECT / DISABLE
Maintenance Disconnect Switch
4090-9005/-9006 Suppression
Release Peripheral
Wire indicator
lamp with 14 AWG
maximum
24 VDC power
for indicator
lamp (2 wires)
Class B NAC wiring
dedicated to Suppression
Release Peripheral
To 4009 IDNet NAC Extender or
4010 Fire Alarm Control Panel
Maximum Notification Appliance Circuit (NAC) Wiring Distances to a Suppression Release Peripheral
(based on a total drop of 3.4V)
RAC Output Current
(refer to solenoid
18 AWG
rating)
0.50 A
250 ft
0.75 A
167 ft
1.00 A
125 ft
Metric wire equivalents: 18 AWG = 0.82 mm
18 AWG
16 AWG
74 ft
23 m
118 ft
50 ft
15 m
79 ft
37 ft
11 m
59 ft
2
; 16 AWG = 1.31 mm
FIRE
RELEASING
NORMAL
DEVICE
0
DISC./
1
DISABLE
FIRE SUPPRESSION
DISCONNECT / DISABLE
Releasing
Appliance Circuit
Addressable devices
IDNet communications,
Class A or Class B
Distance
16 AWG
14 AWG
76 m
399 ft
122 m
635 ft
51 m
266 ft
81 m
423 ft
38 m
199 ft
61 m
317 ft
2
2
; 16 AWG = 1.31 mm
; 14 AWG = 2.08 mm
Distance
14 AWG
36 m
188 ft
57 m
300 ft
24 m
126 ft
38 m
200 ft
18 m
94 ft
29 m
150 ft
2
2
; 14 AWG = 2.08 mm
; 12 AWG = 3.31 mm
A
Blk
Yel
+
Out
-
+
In
-
Blk
Red
MANUAL
RELEASE
12 AWG
194 m
1010 ft
308 m
129 m
673 ft
205 m
97 m
500 ft
154 m
2
2
; 12 AWG = 3.31 mm
5
Total Line
Resistance
12 AWG
1.06 
91 m
0.71 
61 m
0.53 
46 m
2
Listed/approved actuator or
Deluge and Preaction
Automatic Water Control
Valve; one if 24 VDC (or 2 in
series if 12 VDC) per RAC
Valve wiring
junction box
Coil Supervision
Module 2081-9046
COI L SUPERVI S I O N MODULE ( 2 AMP) 2081- 9046
RED
YEL
I N STALLATI O N I N STRUCTI O NS 574- 437 REV
NAC+
MAI N TAI N 1/ 4 " SEPARATI O N
BETW EEN POW ER LI M I T ED
S
( RED/ B LK) AND NONPOW ER
LI M I T ED ( YEL/ B LK) W I R I N G
DATE CODE:
519- 958
BLK
NAC-
BLK
S I M P L E X T I M E R E C O R D E R C O. G A R D N E R MA . U S A
Supervised IAM with
FIRE SUPPRESSION
SYSTEM ABORT
optional Abort Switch
PUSH AND HOLD
FIRE SUPPRESSION
SYSTEM ABORT
Total Line
Resistance
3.58 
PUSH AND HOLD
2.39 
1.79 
2080-9056/-9057 Abort
Switch (as required)
S4010-0003-5 6/2013