Figure 132 2T rack sensors installed on neighboring racks-300mm (12") models

Maximum Depth
1-5/8" (41mm)
FRONT VIEW
12"
(305mm)
Approximate
center of
rack in front
of equipment
Install temperature sensors on the perforated
portion of the rack door using the supplied
wire ties. Ensure door can swing open freely
without binding cables.
The sensors can be set up to either display or control temperature, give them a rack name and draw a
rack layout that can be viewed in the User menu. To do so, go to the Service / Rack Setup Menu of the
Liebert iCOM
®
Sensor wire enters 300mm
(12") Liebert CRV's at rear;
refer to Figure 130.
Each temperature
probe wire is
6ft (1.8m) long
display.
(112mm)
3/16"
(4mm)
(3 3/8")
REAR VIEW
Temperature sensing probes
Bottom inlet see DPN002813 for Air, Water/Glycol
units and DPN002815 for Chilled Water units.
151
Remote Rack Sensor Wiring
4-3/8"
1-5/8"
(41mm) 2 5/8"
86
Cable Connection Entry
Remove terminating
plug. Install terminating
plug into last sensor.
Install CAN cable
into the slot previously
occupied by the
terminating plug.
Liebert IntelliSlot temperature sensor
located in the rear of the unit.
Liebert
(67mm)
Top Inlet
DPN002975
REV 0
®
CRV