Gravity Drain—Units Without Factory-Installed Condensate Pump
• 3/4" FPT drain connection is provided on units without optional factory-installed condensate
pump with infrared humidifier or no humidifier; 1-1/4" FPT connection is provided on units with
steam generating humidifier
• Pitch the drain line toward the drain a minimum of 1/8" (3mm) per 1 foot (305mm) of length
• Drain is trapped internally. Do not trap the drain external to equipment
• Drain line must be sized for 2 gpm (7.6 l/m) flow
Figure 19 Gravity drain piping—600mm (24") and 300mm (12") units