Liebert iCOM
Control
S809 Configuration Safe—Saves or loads configuration settings for the display that have been
modified from the factory defaults to an internal file that can be downloaded / uploaded using the
Liebert iCOM
Service Tool. Selecting Save will write the settings to the internal storage file and
®
selecting Load will write the settings from the internal storage file to the application software. The
internal file is updated automatically every 12 hours.
S810 Network Safe—Saves or loads network settings for the display that have been modified from
the factory defaults to an internal file that can be downloaded / uploaded using the Liebert iCOM
®
Service Tool. Selecting Save will write the settings to the internal storage file and selecting Load will
write the settings from the internal storage file to the application software.
S811 SW Version—Contains the application software version loaded into the Liebert iCOM display.
Figure 109 Service menus—System / network setup parameters-Large display only System - Page 2 for the
Display
S813 IP Address—Contains the network address of the display. This address must be unique to
every other device on the network. This setting is used for the Liebert iCOM board and display
connectivity and for a Liebert iCOM U2U network. Do not use to configure remote monitoring.
S814 Netmask—Divides IP addresses in subnet and specifies the network available to hosts. This
setting is used for Liebert iCOM board and display connectivity and for a Liebert iCOM U2U network.
Do not use to configure remote monitoring.
S815 Gateway—Routes data and acts as a proxy server or a firewall when setting up networks. This
setting is used for the Liebert iCOM board and display connectivity and for a Liebert iCOM U2U
network. Do not use to configure remote monitoring.
S816 MAC (Read Only)—The MAC address is a unique hardware identifier of the Ethernet device.
S817 U2U Protocol (Read Only)—Always set to GBP (Global Bus Protocol).
S818 U2U Address—Unique identifier for each unit on the network. Display addresses range from
33 to 64. Each display on the U2U network must have a different U2U address.
S819 U2U Group—Used to create zones or groups within a U2U network. Once a group number is
selected, the display will see only devices with the same group number. The group number can be
changed to view other devices in different groups.
S820 Bootloader Variables—Indicates whether there has been a change to the bootloader since it
was last loaded, such as monitoring protocol, IP subnet setting, group or U2U number. This
parameter should only be activated by an authorized Liebert Services technician.
®