3.3
Moving the Unit Using Rigging—600mm (24") Models
WARNING
!
Risk of top-heavy unit falling over. Can cause equipment damage, injury and death.
Verify that all lifting equipment is rated for the weight of the unit. See Tables 4 and 5 for
unit weights.
Read all of the following instructions before attempting to move, lift or remove packaging
from the Liebert CRV.
CAUTION
!
Risk of sharp edges, splinters and exposed fasteners. Can cause injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,
shoes and glasses should attempt to move, lift or remove packaging from the Liebert CRV or
prepare the unit for installation.
1. Use a pallet jack or forklift to raise the packaged unit.
2. Place slings under the skid runners, equally spacing the slings to make sure the unit is balanced
(see Figure 8).
3. Lower the unit and remove the pallet jack or forklift.
4. Connect the slings to the lifting device, using spreader bars or similar equipment to protect the
unit (see Figure 8).
NOTE
Wrapping one or two more straps around the middle of the Liebert CRV will improve stability
when it is lifted.
5. Move the unit to its installation location. Two or more properly trained and qualified personnel
are required to move the Liebert CRV to its installation location.
6. Lower the Liebert CRV and remove the slings.
Figure 8
Moving the unit using rigging
®
Liebert
CRV
14
Inspection and Unpacking